Greenheck DOAS v8.1 Reference Manual page 44

Microprocessor controller
Table of Contents

Advertisement

Variable
Space_Dewpoint
Space_Enthalpy
Circuit_A_Superheat
Circuit_B_Superheat
Total_Exhaust_Fan_CFM_BMS
Total_Supply_Fan_CFM_BMS
OAD_CFM_BMS
Active_Temperature_Setpoint
Chilled_Water_1_Valve_Analog_
Output
Electric_Heater_1_Analog_Output Electric Heater 1 Analog Output
Energy_Recovery_Analog_Output Energy Recovery Analog Output
Exhaust_Fan_Speed_Analog_
Output
Hot_Water_Valve_1_Analog_
Output
Mod_Gas_Furnace_1_Analog_
Output
Outside_Air_Damper_Analog_
Output
Supply_Fan_Speed_Analog_
Output
Modulating_Compressor_Analog_
Output_BMS
Circuit_A_Sat_Discharge_
Temperature
Circuit_B_Sat_Discharge_
Temperature
Circuit_A_Sat_Suction_
Temperature
Circuit_B_Sat_Suction_
Temperature
Coil_Temperature_Calculated_
Setpoint
Active_Cooling_Setpoint
Active_Heating_Setpoint
Temperature_Reset_Mode
Temperature_Reset_Mode_
Unoccupied
Active_Temperature_Reset_Mode
Active_Temperature_Reset_Mode_
Unocc
LatestAlm
44
Microprocessor Controller for DOAS
Appendix E: Points List
Description
Space Dewpoint
Space Enthalpy
Circuit A Superheat
Circuit B Superheat
Total Exhaust Fan CFM
Total Supply Fan CFM
OAD CFM
Active Temperature Setpoint
Chilled Water 1 Valve Analog Output
Exhaust Fan Speed Analog Output
Hot Water Valve 1 Analog Output
Mod Gas Furnace 1 Analog Output
Outside Air Damper Analog Output
Supply Fan Speed Analog Output
First Modulating Compressor Analog
Output - BMS
Circuit A Saturated Discharge Temperature
Circuit B Saturated Discharge Temperature
Circuit A Saturated Suction Temperature
Circuit B Saturated Suction Temperature
Calculated Coil Leaving Setpoint
Active Cooling Setpoint
Active Heating Setpoint
"Occupied Reset Type Setpoint
1-No Reset(Supply Temp Control) 2-Space
3-Return 4-Outside"
"Unoccupied Reset Type Setpoint
1-No Reset(Supply Temp Control) 2-Space
3-Return 4-Outside"
"Active Occupied Reset Type Setpoint
1-No Reset(Supply Temp Control) 2-Space
3-Return 4-Outside"
"Active Unoccupied Reset Type Setpoint
1-No Reset(Supply Temp Control) 2-Space
3-Return 4-Outside"
Most recent alarm - See Alarm Table
BACnet Modbus
Read
or
Object
Register
Write
AV-58
30128
R
AV-59
30130
R
AV-60
30132
R
AV-61
30134
R
AV-64*
30140
R
AV-65*
30142
R
AV-66*
30144
R
AV-67*
30146
R
AV-68
30148
R
AV-70
30152
R
AV-72*
30156
R
AV-73*
30158
R
AV-74
30160
R
AV-76
30164
R
AV-78*
30168
R
AV-79*
30170
R
AV-80
30172
R
AV-82
30176
R
AV-83
30178
R
AV-86
30184
R
AV-87
30186
R
AV-90
30192
R
AV-91
30194
R
AV-92
30196
R
IV-1*
40080
RW
IV-2*
40082
RW
IV-3
30198
R
IV-4
30200
R
IV-5*
30202
R
Text or Unit of M
Active Inactive
°F
btu/lb
°F
°F
cfm
cfm
cfm
°F
%
%
%
%
%
%
%
%
%
°F
°F
°F
°F
°F
°F
°F
Integer
Integer
Integer
Integer
Integer