Greenheck DOAS v8.1 Reference Manual page 33

Microprocessor controller
Table of Contents

Advertisement

Menu
c
b
F
reaTing a
ackup
ile
Important:
• At first startup or commissioning, or prior to communicating with Technical
Support about performance issues, we recommend creating a backup file for
each controller.
• Name each file with the unit sales order–line number found on the silver
nameplate attached to the electrical access door.
• Also consider creating a backup file whenever significant program changes are
made.
To create a system backup file using the handheld or virtual keypad/display
buttons:
1. Go to the Main Menu/Ctrl Variables/Advanced/Login screen. Press the Enter
and Up or Down arrow buttons to enter the service password, which is 9998.
2. Go to the Main Menu/Ctrl Variables/Advanced/Backup/Restore screen.
3. Press the Up or Down arrow buttons to navigate to the Backup Settings screen.
4. Press the Enter and Up or Down arrow buttons to select the backup location
(internal memory or USB). If creating a backup to a USB drive, insert a USB
drive into the main controller.
5. Press Enter to highlight and then the Up or Down arrow buttons to fill the Save
checkbox. This action creates the backup file.
r
b
esToring From a
ackup
From USB
1. Place the restore file in the root directory of a USB drive. (Do not place the file
within a folder on the USB drive.) The file must be named: User_Backup.txt
2. Insert the USB drive into the controller's USB port.
3. Go to the Main Menu/Unit Enable screen. Press the Enter and Up or Down
arrow buttons to disable the unit.
4. Go to the Main Menu/Ctrl Variables/Advanced/Login screen. Press the Enter
and Up or Down arrow buttons to enter the service password (9998).
5. Go to the Main Menu/Ctrl Variables/Advanced/Backup/Restore screen.
6. Press the Up or Down arrow buttons to navigate to the USB Restore screen.
7.
Press Enter to highlight and then the Up or Down arrow buttons to fill the
Restore checkbox. This action restores the backup file. If there is an error
during the process, the specific error is displayed on this screen.
8. Controller will automatically restart.
From internal memory
1. Go to the Main Menu/Unit Enable screen. Press the Enter and Up or Down
arrow buttons to disable the unit.
2. Go to the Main Menu/Ctrl Variables/Advanced/Login screen. Press the Enter
and Up or Down arrow buttons to enter the service password, which is 9998.
3. Go to the Main Menu/Ctrl Variables/Advanced/Backup/Restore screen.
4. Press the Up or Down arrow buttons to navigate to the Internal Restore
screen. This screen is only available when a backup file exists in internal
memory.
5. Press Enter to highlight and then the Up or Down arrow buttons to fill the
Restore checkbox. This action restores the backup file. If there is an error
during the process, the specific error is displayed on this screen.
6. Controller will automatically restart.
F
ile
Microprocessor Controller for DOAS
33