Greenheck DOAS v8.1 Reference Manual page 42

Microprocessor controller
Table of Contents

Advertisement

Variable
Aux_In_Customer_6
Aux_In_Customer_7
Aux_In_Customer_8
Aux_In_Customer_9
Aux_In_Customer_10
Temperature_Setpoint
Temperature_Heat_Cool_
Deadband
Temperature_Setpoint_
Unoccupied
Temperature_Heat_Cool_
Deadband_Unoccupied
Cooling_Coil_Setpoint_Min
Cooling_Coil_Setpoint_Max
Dehumidification_Setpoint
Outside_Dewpoint_Setpoint
Indoor_Dewpoint_Setpoint
Unocc_Indoor_Dewpoint_Setpoint
Unoccupied_Dehumidification_
Setpoint
Economizer_Temp_Enable_
Setpoint
Economizer_Enthalpy_Enable_
Setpoint
Supply_Fan_CFM_Setpoint
Exhaust_Fan_CFM_Setpoint
OAD_CFM_Setpoint
Cooling_Lockout_Setpoint
Heating_Lockout_Setpoint
Preheat_Lockout_Setpoint
Economizer_Lockout_Setpoint
Return_Duct_Static_Pressure_
Setpoint
Space_Static_Pressure_Setpoint
Supply_Duct_Static_Pressure_
Setpoint
42
Microprocessor Controller for DOAS
Appendix E: Points List
Description
Customer defined auxiliary input
Customer defined auxiliary input
Customer defined auxiliary input
Customer defined auxiliary input
Customer defined auxiliary input
"Main Temperature Set point
Supply, Space, or Return target
temperature"
Heat/Cool Spt Deadband when Room
or Return control is active Clg Spt =
Deadband /2 + Temp Spt Htg Spt =
Deadband /2 - Temp Spt
Main Temperature Set point Supply, Space,
or Return target temperature
Heat/Cool Spt Deadband when Room
or Return control is active Clg Spt =
Deadband /2 + Temp Spt Htg Spt =
Deadband /2 - Temp Spt
Cooling Coil Leaving Air Setpoint
Maximum Coil Leaving Setpoint
Dehumidification Setpoint %RH for Space
or Return control
Outside Dewpoint Dehumidification Trigger
Indoor Dewpoint Dehumidification Trigger
Unoccupied Indoor Dewpoint
Dehumidification Trigger
Unoccupied Dehumidification %RH
Setpoint
"Economizer Ambient Temp Enable
Setpoint
Allow Econ when OAT< Setpoint"
"Economizer Enthalpy Enable Setpoint
Allow Econ when OA Enthalpy<Setpoint"
Supply Fan CFM Setpoint
Exhaust Fan CFM Setpoint
OAD CFM Setpoint
Cooling Ambient Lockout Setpoint
Heating Ambient Lockout Setpoint
Preheat Ambient Lockout Setpoint
Economizer Ambient Lockout Setpoint
Return Duct Static Pressure Setpoint
Space Static Pressure Setpoint
Supply Duct Static Pressure Setpoint
BACnet Modbus
Read
or
Object
Register
Write
AI-41*
30082
R
AI-42
30084
R
AI-43
30086
R
AI-44
30088
R
AI-45
30090
R
AV-1*
40002
RW
AV-2
40004
RW
AV-3*
40006
RW
AV-4
40008
RW
AV-5
40010
RW
AV-6
40012
RW
AV-7
40014
RW
AV-8
40016
RW
AV-9
40018
RW
AV-10
40020
RW
AV-11
40022
RW
AV-12
40024
RW
AV-13
40026
RW
AV-14
40028
RW
AV-15
40030
RW
AV-16
40032
RW
AV-17
40034
RW
AV-18
40036
RW
AV-19
40038
RW
AV-20
40040
RW
AV-21*
40042
RW
AV-22*
40044
RW
AV-23*
40046
RW
Text or Unit of M
Active Inactive
selectable
selectable
selectable
selectable
selectable
°F
Delta in °F
°F
Delta in °F
°F
°F
%
°F
°F
°F
%
°F
btu/lb
cfm
cfm
cfm
°F
°F
°F
°F
"wc
"wc
"wc