E: Points List - Greenheck DOAS v8.1 Reference Manual

Microprocessor controller
Table of Contents

Advertisement

Variable
Space_Temp_Analog_Input
Supply_Temp_Analog_Input
Outside_Air_Temp_Analog_Input
Mixed_Temp_Analog_Input
Cold_Coil_1_Temp_Analog_Input
Return_Temp_Analog_Input
Exhaust_Temp_Analog_Input
Space_RH_Analog_Input
Outside_RH_Analog_Input
Return_RH_Analog_Input
Return_Duct_Static_Pressure_
Analog_Input
Space_Static_Pressure_Analog_
Input
Supply_Duct_Static_Pressure_
Analog_Input
Space_CO2_1_Analog_Input
Space_CO2_2_Analog_Input
Return_CO2_Analog_Input
CL_Coil_Spt_Temp
CL_Supply_Spt_Temp
Circuit_A_Discharge_Temp_
Analog_Input
Circuit_A_Suction_Temp_Analog_
Input
Circuit_B_Discharge_Temp_
Analog_Input
Circuit_B_Suction_Temp_Analog_
Input
Circuit_A_Discharge_Pressure_
Analog_Input
Circuit_A_Suction_Pressure_
Analog_Input
Circuit_B_Discharge_Pressure_
Analog_Input
Circuit_B_Suction_Pressure_
Analog_Input
Aux_In_Customer_1
Aux_In_Customer_2
Aux_In_Customer_3
Aux_In_Customer_4
Aux_In_Customer_5
Appendix E: Points List
Description
Space Temperature
Supply Temperature
Outside Air Temperature
Mixed Temperature
Cold Coil 1 Temperature
Return Temperature
Exhaust Temperature
Space % Relative Humidity
Outside % Relative Humidity
Return % Relative Humidity
Return Duct Static Pressure
Space Static Pressure
Supply Duct Static Pressure
Space 1 CO2 ppm
Space 2 CO2 ppm
Return CO2 ppm
Heat Cool Only - Cooling Coil Setpoint
Input
Heat Cool Only - Supply Setpoint
Temperature
Circuit A Discharge Temperature
Circuit A Suction Temperature
Circuit B Discharge Temperature
Circuit B Suction Temperature
Circuit A Discharge Pressure
Circuit A Suction Pressure
Circuit B Discharge Pressure
Circuit B Suction Pressure
Customer defined auxiliary input
Customer defined auxiliary input
Customer defined auxiliary input
Customer defined auxiliary input
Customer defined auxiliary input
BACnet Modbus
Read
or
Object
Register
Write
AI-1*
30002
R
AI-2*
30004
R
AI-3*
30006
R
AI-4*
30008
R
AI-5*
30010
R
AI-7*
30014
R
AI-8*
30016
R
AI-9*
30018
R
AI-10*
30020
R
AI-11*
30022
R
AI-12*
30024
R
AI-13*
30026
R
AI-14*
30028
R
AI-15*
30030
R
AI-16
30032
R
AI-17*
30034
R
AI-18*
30036
R
AI-19*
30038
R
AI-20
30040
R
AI-21
30042
R
AI-22
30044
R
AI-23
30046
R
AI-28
30056
R
AI-29
30058
R
AI-30
30060
R
AI-31
30062
R
AI-36*
30072
R
AI-37*
30074
R
AI-38*
30076
R
AI-39*
30078
R
AI-40*
30080
R
Microprocessor Controller for DOAS
Text or Unit of M
Active Inactive
°F
°F
°F
°F
°F
°F
°F
%
%
%
"wc
"wc
"wc
ppm
ppm
ppm
2-10V = 50-75°F
2-10V = 50-95°F
°F
°F
°F
°F
psig
psig
psig
psig
selectable
selectable
selectable
selectable
selectable
41