Technical specifications
8.1 Technical specifications
Article number
Permissible potential difference
between different circuits
Ambient conditions
Ambient temperature during operation
Dimensions
Width
Height
Depth
Weights
Weight, approx.
Cycle time
The cycle time describes the time slice in which new process values are output.
The cycle time is the sum of the basic cycle times and the channel processing times (independent
of parameter assignment).
Basic cycle time
Channel processing time 0.03 ms
Cycle time = Basic cycle time + n × Channel processing time
Redundancy failover time
In error-free IO redundancy mode, both I/O modules output half the specified current. If one I/O
module fails, failover to the partner module occurs and the partner module outputs the full
current.
The maximum redundancy failover time of the I/O module is 2 ms.
48
between the channels and backplane bus
between the channels and the power supply
of the electronics
horizontal installation, min.
horizontal installation, max.
vertical installation, min.
vertical installation, max.
Without HART protocol With HART protocol
0.6 ms
6DL1135-6UD00-0PK0
Yes; 125 V AC / 150 V DC
Yes; 125 V AC / 150 V DC
125 V AC / 150 V DC between the channels, 125 V
AC / 150 V DC between the channels and backplane
bus/supply voltage
-40 °C
70 °C; Observe derating
-40 °C
60 °C; Observe derating
22.5 mm
115 mm
138 mm
165 g
and multiHART
0.9 ms
0.1 ms
Equipment Manual, 07/2022, A5E50102497-AB
With HART protocol
and
8 HART variables
1.0 ms
0.1 ms
AQ 4xI HART ISOL HA