Camus Hydronics MICOFLAME GRANDE Series Installation, Operation And Service Manual page 15

Gas fired commercial copper tube boilers
Table of Contents

Advertisement

Room Air, Vent Terminal Clearances
Clearance above grade, veranda, porch,
A
deck, or balcony
Clearance to window or door that may be
B
opened
C
Clearance to permanently closed window
Vertical clearance to ventilated soffit located
above the terminal within a horizontal
D
distance of 2 ft. (61 cm) from the center line
of the terminal
E
Clearance to unventilated soffit
F
Clearance to outside corner
G
Clearance to inside corner
Clearance to each side of center line
H
extended above meter/ regulator assembly
Clearance to service regulator vent outlet
I
Clearance to nonmechanical air supply inlet
J
to building or the combustion air inlet to any
other appliance
Clearance to a mechanical air supply inlet
K
Clearance above paved sidewalk or paved
L
driveway located on public property
Clearance under veranda, porch deck, or
M
balcony
1
In accordance with the current CSA B149.1 Natural Gas and Propane Installation Code
2
In accordance with ANSI Z223.1/ NFPA 54 National Fuel Gas Code
α
A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single
family dwellings and serves both dwellings
β
Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the
floor.
* For clearances not specified in ANSI Z223.1/ NFPA 54 or CSA-B149.1. Clearance in accordance with local
installation codes and the requirements of the gas supplier
Canadian Installations
12" (30 cm)
36" (91 cm)
*
*
*
*
*
*
Above a regulator within
3
feet
(91
horizontally of the vertical
center
line
of
regulator vent outlet to a
maximum
distance of 15' (4.5 m)
36" (91cm)
6 ft. (1.83 m)
α
7 ft. (2.13 m)
β
12" (30 cm)
11
1
US Installations
12 in (30 cm)
4' (1.2 m) below or to
side of opening; 1' (30
cm) above opening
*
*
*
*
*
*
4 ft. (1.2m) below or to
cm)
side of opening; 1 ft. (300
mm) above opening
the
vertical
4 ft. (1.2 m) below or to
side of opening; 1ft (30
cm) above opening
3 ft. (91 cm) above if
within 10 ft. (3 m)
horizontally
α
7 ft. (2.13 m)
*
2