Camus Hydronics MICOFLAME GRANDE Series Installation, Operation And Service Manual page 14

Gas fired commercial copper tube boilers
Table of Contents

Advertisement

Direct Vent Terminal Clearances
Clearance above grade, veranda, porch,
A
deck, or balcony
Clearance to window or door that may be
B
opened
Clearance to window or door that may be
C
opened
Vertical clearance to ventilated soffit located
above the terminal within a horizontal
D
distance of 2 ft. (61cm) from the center line
of the terminal.
E
Clearance to unventilated soffit
F
Clearance to outside corner
G
Clearance to inside corner
Clearance to each side of center line
H
extended above meter/ regulator assembly
I
Clearance to service regulator vent outlet
Clearance to nonmechanical air supply inlet
J
to building or the combustion air inlet to any
other appliance
Clearance to a mechanical air supply inlet
K
Clearance above paved sidewalk or paved
L
driveway located on public property
Clearance under veranda, porch deck, or
M
balcony
1
In accordance with the current CSA B149.1 Natural Gas and Propane Installation Code
2
In accordance with ANSI Z223.1/ NFPA 54 National Fuel Gas Code
α
A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single
family dwellings and serves both dwellings
β
Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the
floor.
* For clearances not specified in ANSI Z223.1/ NFPA 54 or CSA-B149.1. Clearance in accordance with local
installation codes and the requirements of the gas supplier
Canadian Installations
12" (30 cm)
36" (91 cm)
*
*
*
*
*
*
36" (91 cm)
36" (91cm)
6' (1.83 m)
α
7' (2.13 m)
β
12" (30 cm)
10
1
2
US Installations
12 in (30 cm)
12" (30 cm)
*
*
*
*
*
*
*
12" (30 cm)
3' (91 cm) above if within
10' (3 m) horizontally
*
*