Napoleon Luxuri Series Installation Manual page 56

Table of Contents

Advertisement

fi nish framing - after appliance installation
EN
single-sided recessed
WARNING
!
Shaded components (fi nish framing) must be non-combustible materials.
note:
Finish framing must be built after
appliance has been placed in its
fi nal position and venting con-
nected.
This confi guration also re-
quires recess area to use
non-combustible facing due to
close proximity to vent.
The LVX series requires a mini-
mum enclosure height, as illus-
trated (dimension L), measured
from the bottom of the appliance.
For temperature requirements,
this area must be left unobstruct-
ed. Some venting confi gurations
that require more vertical rise will
require a larger enclosure to pro-
vide minimum vertical clearance
between vent pipes and combus-
tibles.
Option 2 illustrated (appliance not shown)
minimum framing
Ref
K
E***
F
53 13/16" (136.7cm)
J
L
Q*
(Q x R)*
M**
* ONLY APPLICABLE TO OPTION 2 AND 3 - Opening must be centered in enclosure on appliance. Dimensions represent
fi nished sizes and where applicable should be adjusted to include fi nish material thickness.
** Can only be increased to 4" max by building a protrusion.
***Max. 21" (53.5cm).
56
W415-2035 / C / 04.30.21
Ceiling
J
LVX38-1
LVX50-1
65 13/16" (167.2cm)
Optional - Appliance does not need to be elevated above fl oor
73" (185.4cm)
80 sq. in.
R
Q
L
M
F
E
LVX62-1
39 15/16" (101.4cm)
18" (45.7cm)
77 13/16" (197.6cm)
2" min and 3" max
3" (76mm)
K
Drywall
Insulation
LVX74-1
89 13/16" (228.1cm)
91" (231.1cm)
160 sq. in.