Protected Related Functions; Dr.rdre1 Disturbance Recorder Values; Ld0.Secrsyn1 Synchrocheck Line And Bus State; Physical And Raw I/O Data - ABB Relion 620 Series Manual

Transformer protection and control
Hide thumbs Also See for Relion 620 Series:
Table of Contents

Advertisement

1MRS757660 A
2.5.6
2.5.6.1
Table 173:

DR.RDRE1 Disturbance recorder values

IEC 61850 name
SA name
DR.RDRE1
.FltNum.stVal
.MemUsed.stVal
2.5.6.2
Table 174:

LD0.SECRSYN1 Synchrocheck line and bus state

IEC 61850 name
SA name
LD0.SECRSYN1
.EnSt.stVal
2.5.7
2.5.7.1
Table 175:

LD0.XRGGIO105 RTD inputs

IEC 61850 name
SA name
LD0.XRGGIO105
.AnIn1.instMag
.AnIn2.instMag
.AnIn3.instMag
.AnIn4.instMag
.AnIn5.instMag
.AnIn6.instMag
.AnIn7.instMag
.AnIn8.instMag
RET620
Point List Manual

Protected related functions

DR.RDRE1 Disturbance recorder values
Description
-
Number of recordings
-
Rec. memory used
LD0.SECRSYN1 Synchrocheck line and bus state
Description
-
Energization state

Physical and raw I/O data

LD0.XRGGIO105 RTD inputs
Description
AI_VAL1
RTD input 1
AI_VAL2
RTD input 2
AI_VAL3
RTD input 3
AI_VAL4
RTD input 4
AI_VAL5
RTD input 5
AI_VAL6
RTD input 6
AI_VAL7
RTD input 7
AI_VAL8
RTD input 8
DNP3 data mappings
Values
S
Arg 1,2,3,4
0...65535
R
0,65535,0,65535
0...100 [%]
R
0,100,0,100
Values
S
Arg 1,2,3,4
0...4
R
0,4,0,4
Values
S
Arg 1,2,3,4
-10000...
10000
R
-1E4,1E4,-1E4,1E4
-10000...
10000
R
-1E4,1E4,-1E4,1E4
-10000...
10000
R
-1E4,1E4,-1E4,1E4
-10000...
10000
R
-1E4,1E4,-1E4,1E4
-10000...
10000
R
-1E4,1E4,-1E4,1E4
-10000...
10000
R
-1E4,1E4,-1E4,1E4
-10000...
10000
R
-1E4,1E4,-1E4,1E4
-10000...
10000
R
-1E4,1E4,-1E4,1E4