Section 2
DNP3 data mappings
2.5.3.3
Table 162:
LD0.TPOSSLTC1 Tap changer position value
IEC 61850 name
LD0.TPOSSLTC1
.TapPos.valWTr.posVal
2.5.4
2.5.4.1
Table 163:
LD0.CMMXU1 Phase currents (1)
IEC 61850 name
LD0.CMMXU1
.A.phsA.instCVal.mag
.A.phsB.instCVal.mag
.A.phsC.instCVal.mag
2.5.4.2
Table 164:
LD0.CMMXU2 Phase currents (2)
IEC 61850 name
LD0.CMMXU2
.A.phsA.instCVal.mag
.A.phsB.instCVal.mag
.A.phsC.instCVal.mag
2.5.4.3
Table 165:
LD0.CSMSQI1 Sequence of currents
IEC 61850 name
LD0.CSMSQI1
.SeqA.c1.instCVal.mag
.SeqA.c2.instCVal.mag
.SeqA.c3.instCVal.mag
66
LD0.TPOSSLTC1 Tap changer position value
SA name
Description
TAP_POS
Tap changer position
Metering and measurand functions
LD0.CMMXU1 Phase currents (1)
SA name
Description
Phase-to-ground current
I_INST_A
-phsA magnitude
I_INST_B
-phsB magnitude
I_INST_C
-phsC magnitude
LD0.CMMXU2 Phase currents (2)
SA name
Description
Phase-to-ground current
I_INST_A
-phsA magnitude
I_INST_B
-phsB magnitude
I_INST_C
-phsC magnitude
LD0.CSMSQI1 Sequence of currents
SA name
Description
Sequence of currents
I1_INST
-Positive magnitude
I2_INST
-Negative magnitude
I3_INST
-Zero magnitude
Values
S
Arg 1,2,3,4
-64...63
R
-64,63,-64,63
Values
S
Arg 1,2,3,4
0.00..40.0 [xIn]
R
0,40,0,4000
0.00..40.0 [xIn]
R
0,40,0,4000
0.00..40.0 [xIn]
R
0,40,0,4000
Values
S
Arg 1,2,3,4
0.00..40.0 [xIn]
R
0,40,0,4000
0.00..40.0 [xIn]
R
0,40,0,4000
0.00..40.0 [xIn]
R
0,40,0,4000
Values
S
Arg 1,2,3,4
0.00..40.0 [xIn]
R
0,40,0,4000
0.00..40.0 [xIn]
R
0,40,0,4000
0.00..40.0 [xIn]
R
0,40,0,4000
1MRS757660 A
RET620
Point List Manual