Ld0.Rescmmxu1 Residual Current (1); Ld0.Rescmmxu2 Residual Current (2); Ld0.Vmmxu1 Voltage Measurement; Ld0.Resvmmxu1 Residual Voltage (1) - ABB Relion 620 Series Manual

Transformer protection and control
Hide thumbs Also See for Relion 620 Series:
Table of Contents

Advertisement

1MRS757660 A
2.5.4.4
Table 166:

LD0.RESCMMXU1 Residual current (1)

IEC 61850 name
SA name
LD0.RESCMMXU1
.A.res.instCVal.mag
2.5.4.5
Table 167:

LD0.RESCMMXU2 Residual current (2)

IEC 61850 name
SA name
LD0.RESCMMXU2
.A.res.instCVal.mag
2.5.4.6
Table 168:

LD0.VMMXU1 Voltage measurement

IEC 61850 name
SA name
LD0.VMMXU1.PhV
.phsA.cVal.mag
.phsB.cVal.mag
.phsC.cVal.mag
LD0.VMMXU1.PPV
.phsAB.cVal.mag
.phsBC.cVal.mag
.phsCA.cVal.mag
2.5.4.7
Table 169:

LD0.RESVMMXU1 Residual voltage (1)

IEC 61850 name
SA name
LD0.RESVMMXU1
.PhV.res.instCVal.mag
RET620
Point List Manual
LD0.RESCMMXU1 Residual current (1)
Description
I0_INST
Residual current
LD0.RESCMMXU2 Residual current (2)
Description
I0_INST
Residual current
LD0.VMMXU1 Voltage measurement
Description
Phase-to-ground voltage
U_DB_A
-phsA magnitude
U_DB_B
-phsB magnitude
U_DB_C
-phsC magnitude
Phase-to-phase voltage
U_DB_AB
-phsAB magnitude
U_DB_BC
-phsBC magnitude
U_DB_CA
-phsCA magnitude
LD0.RESVMMXU1 Residual voltage (1)
Description
U0_INST
Residual voltage
DNP3 data mappings
Values
S
Arg 1,2,3,4
0.00..40.0 [xIn]
R
0,40,0,4000
Values
S
Arg 1,2,3,4
0.00..40.0 [xIn]
R
0,40,0,4000
Values
S
Arg 1,2,3,4
0.00...4.00
[xUn]
R
0,4,0,400
0.00...4.00
[xUn]
R
0,4,0,400
0.00...4.00
[xUn]
R
0,4,0,400
0.00...4.00
[xUn]
R
0,4,0,400
0.00...4.00
[xUn]
R
0,4,0,400
0.00...4.00
[xUn]
R
0,4,0,400
Values
S
Arg 1,2,3,4
0.00..4.00
[xUn]
R
0,4,0,400
Section 2
67

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ret620

Table of Contents