Ld0.Lphd1 System Values; Ld0.Ledggio1 Lhmi Led Indications (3 States); Ld0.Dnpggio1 Active Parameter Setting Group - ABB Relion 620 Series Manual

Transformer protection and control
Hide thumbs Also See for Relion 620 Series:
Table of Contents

Advertisement

1MRS757660 A
2.5.1.2
Table 143:

LD0.LPHD1 System values

IEC 61850 name
SA name
LD0.LPHD1
.NumCmpChg.stVal
.NumPwrUp.stVal
.PhyHealth1.stVal
.PhyHealth2.stVal
.WacTrg.stVal
.WrmStr.stVal
2.5.1.3
Table 144:

LD0.LEDGGIO1 LHMI LED indications (3 states)

IEC 61850 name
SA name
LD0.LEDGGIO1
.ISCSO1.stVal
.ISCSO2.stVal
.ISCSO3.stVal
.ISCSO4.stVal
.ISCSO5.stVal
.ISCSO6.stVal
.ISCSO7.stVal
.ISCSO8.stVal
.ISCSO9.stVal
.ISCSO10.stVal
.ISCSO11.stVal
2.5.1.4
Table 145:

LD0.DNPGGIO1 Active parameter setting group

IEC 61850 name
SA name
LD0.DNPGGIO1
.ActSG.stVal
RET620
Point List Manual
LD0.LPHD1 System values
Description
-
Num.of comp. changes
-
Num.of power ups
Warning
Warning code
Internal Fault
Internal fault code
-
Num.of watchdog resets
-
Num.of warm starts
LD0.LEDGGIO1 LHMI LED indications (3 states)
Description
-
LED 1 state
-
LED 2 state
-
LED 3 state
-
LED 4 state
-
LED 5 state
-
LED 6 state
-
LED 7 state
-
LED 8 state
-
LED 9 state
-
LED 10 state
-
LED 11 state
LD0.DNPGGIO1 Active parameter setting group
Description
-
Active setting group
DNP3 data mappings
Values
S
Arg 1,2,3,4
0...65535
R
0,65535,0,65535
0...65535
R
0,65535,0,65535
0...65535
R
0,65535,0,65535
0...65535
R
0,65535,0,65535
0...65535
R
0,65535,0,65535
0...65535
R
0,65535,0,65535
Values
S
Arg 1,2,3,4
0/1/3=Off/Ok/
Alarm
R
0,3,0,3
0/1/3=Off/Ok/
Alarm
R
0,3,0,3
0/1/3=Off/Ok/
Alarm
R
0,3,0,3
0/1/3=Off/Ok/
Alarm
R
0,3,0,3
0/1/3=Off/Ok/
Alarm
R
0,3,0,3
0/1/3=Off/Ok/
Alarm
R
0,3,0,3
0/1/3=Off/Ok/
Alarm
R
0,3,0,3
0/1/3=Off/Ok/
Alarm
R
0,3,0,3
0/1/3=Off/Ok/
Alarm
R
0,3,0,3
0/1/3=Off/Ok/
Alarm
R
0,3,0,3
0/1/3=Off/Ok/
Alarm
R
0,3,0,3
Values
S
Arg 1,2,3,4
1...6
R
1,6,1,6
Section 2
61

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ret620

Table of Contents