Section 2
DNP3 data mappings
2.3.8
2.3.8.1
Table 81:

DR.RDRE1 Disturbance recorder

IEC 61850 name
DR.RDRE1
.RcdMade.stVal
2.3.8.2
Table 82:

LD0.SECRSYN1 Synchrocheck

IEC 61850 name
LD0.SECRSYN1
.SynPrg.stVal
.FailCmd.stVal
.FailSyn.stVal
2.3.8.3
Table 83:

LD0.CCRDIF1 Current circuit failure protection

IEC 61850 name
LD0.CCRDIF1
.Alm.stVal
.Op.general
2.3.8.4
Table 84:

LD0.CCRDIF2 Current circuit failure protection

IEC 61850 name
LD0.CCRDIF2
.Alm.stVal
.Op.general
2.3.8.5
Table 85:

LD0.CTSRCTF1 Current circuit supervision for transformers (1)

IEC 61850 name
CTRL.CTSRCTF1
.Alm.stVal
.Op.general
42

Protection related functions

DR.RDRE1 Disturbance recorder
SA name
LD0.SECRSYN1 Synchrocheck
SA name
SYNC_INPRO
CMD_FAIL_AL
CL_FAIL_AL
LD0.CCRDIF1 Current circuit failure protection
SA name
FAIL
ALARM
LD0.CCRDIF2 Current circuit failure protection
SA name
FAIL
ALARM
LD0.CTSRCTF1 Current circuit supervision for transformers (1)
SA name
Description
DR recording made
Description
Synch in progress
CB close request failed
CB close command failed
Description
Fail Alarm
Fail Operate
Description
Fail Alarm
Fail Operate
Description
Alarm output
CT secondary failure
1MRS757660 A
Values
1=Made
Values
1=In progress
1=Failed
1=Failed
Values
1=Alarm
1=Operate
Values
1=Alarm
1=Operate
Values
1 = Alarm
1 = Failure
RET620