Section 2
DNP3 data mappings
2.3.3
2.3.3.1
Table 14:

LD0.ARCSARC1 Fault arc protection stage 1

IEC 61850 name
LD0.ARCSARC11
.FADet.stVal
LD0.ARCPTRC11
.Op.general
2.3.3.2
Table 15:

LD0.ARCSARC2 Fault arc protection stage 2

IEC 61850 name
LD0.ARCSARC21
.FADet.stVal
LD0.ARCPTRC21
.Op.general
2.3.3.3
Table 16:

LD0.ARCSARC3 Fault arc protection stage 3

IEC 61850 name
LD0.ARCSARC31
.FADet.stVal
LD0.ARCPTRC31
.Op.general
2.3.3.4
Table 17:

LD0.SSCBR1 Circuit-breaker condition monitoring

IEC 61850 name
.APwrAlm.stVal
.APwrLO.stVal
.CBLifAlm.stVal
.ClsAlm.stVal
.LonTmAlm.stVal
.OpnAlm.stVal
.OpNumAlm.stVal
Table continues on next page
26

Sensors and monitoring functions

LD0.ARCSARC1 Fault arc protection stage 1
SA name
ARC_FLT_DET
OPERATE
LD0.ARCSARC2 Fault arc protection stage 2
SA name
ARC_FLT_DET
OPERATE
LD0.ARCSARC3 Fault arc protection stage 3
SA name
ARC_FLT_DET
OPERATE
LD0.SSCBR1 Circuit-breaker condition monitoring
SA name
IPOW_ALM
IPOW_LO
CB_LIFE_ALM
TRV_T_CL_ALM
MON_ALM
TRV_T_OP_ALM
OPR_ALM
Description
Arc detected
Operate
Description
Arc detected
Operate
Description
Arc detected
Operate
Description
Iyt alarm
Iyt lockout
CB lifetime alarm
Cls travel time alarm
CB inactive alarm
Cls travel time alarm
CB operations alarm
1MRS757660 A
Values
1=Detected
1=Operate
Values
1=Detected
1=Operate
Values
1=Detected
1=Operate
Values
1=Alarm
1=Lockout
1=Alarm
1=Alarm
1=Alarm
1=Alarm
1=Alarm
RET620