Overview

This document describes the DNP3 data points and structures available in the IED.
The data points are unmapped as a default on the DNP3 level. The point lists
describe a superset of all DNP3 data available through the standard configuration/s
including the optional functionalities.
The point tables show all the available DNP3 data points in the IEDs. The data
objects in the point tables are listed based on the AFL and data object IEC 61850
names.
As a default, the class assignments are Class 0 and Class 1 for binary inputs and
Class 0 and Class 2 for analog inputs. These assignments can be modified later.
Analog values are provided with default scalings. The scalings can be freely
modified by the user.
This list represents the superset of DNP3 points. The actual set of available points,
meaning the actual set of available applications, is determined by the IED's order
code.

Supported functions

Table 2:
Supported functions in RET620
Function block
PHLPTOC1
PHLPTOC2
PHHPTOC1
PHHPTOC2
PHIPTOC1
PHIPTOC2
DPHLPDOC1
DPHHPDOC1
EFLPTOC1
EFLPTOC2
EFHPTOC1
EFHPTOC2
DEFLPDEF1