Circuit Breaker Accessory And Installation - Eaton IZM6 Series Operating Instruction

Air circuit breaker
Hide thumbs Also See for IZM6 Series:
Table of Contents

Advertisement

Instruction Leafl et
Effective September 2022

Circuit breaker accessory and installation

Closing coil
After charging, the closing coil enables the energy stored in the
operating mechanism to release instantaneously, allowing the cir-
cuit breaker to close quickly.
• IZM65/67/69
Power loss table of the closing coil
Insulation
voltage
Rated control
(U
)
voltage U
(V)
i
s
400V
AC230
AC400
AC110
DC110
DC220
Shunt Coil
The shunt coil enables the circuit breaker to open remotely.
• IZM65/67/69
Power consumption of the shunt coil
Insulation
voltage
Rated control
(U
)
voltage U
(V)
i
s
400V
AC230
AC400
AC110
DC110
DC220
10
EATON www.eaton.com
GB29.2 2×M4×62
GB93 2× 4
GB97 2× 4
Pickup
Actuating
transient
voltage
current
(0.85~1.1) U
2.8A
s
(0.85~1.1) U
2.1A
s
(0.85~1.1) U
5.1A
s
(0.85~1.1) U
5.2A
s
(0.85~1.1) U
2.9A
s
GB29.2 2×M4×62
GB93 2× 4
GB97 2× 4
Pickup
Actuating
transient
voltage
current
(0.7~1.1) U
2.8A
s
(0.7~1.1) U
2.1A
s
(0.7~1.1) U
5.1A
s
(0.7~1.1) U
5.2A
s
(0.7~1.1) U
2.9A
s
Motor operator
The circuit breaker offers motor charging and automatic recharging
functions (manual charging is also available for the circuit breaker).
• IZM65/67/69
Rated control voltage
U
(V)
s
Pickup
Model code
transient
power
Actuating
voltage
575VA
Power loss
2500A frame 150VA
780VA
4000A frame 150VA
495VA
6300A frame 180VA
550W
Charging time (s)
630W
Pickup
transient
power
575VA
780VA
495VA
550W
630W
IZM6 Series Air Circuit Breaker
Operating Instruction Leafl et
GB819 2×M4×10
GB5783 M6×60
GB93
6
GB97
6
AC230
AC400
DC110
M1
M2
M3
(0.85~1.1) U
(0.85~1.1) U
(0.85~1.1) U
s
s
150VA
150W
150VA
150W
180VA
180W
5s
5s
5s
DC220
M4
(0.85~1.1) U
s
s
150W
150W
180W
5s

Advertisement

Table of Contents
loading

This manual is also suitable for:

Izm65Izm67Izm69

Table of Contents