Other protection characteristics of the intelligent con-
troller
Under voltage protection
The intelligent controller measures the RMS value of the primary
circuit voltage. When the three line voltages are all less than
the set point, that is, when the maximum value of the three line
voltages is less than the under voltage protection set point, the
undervoltage protection will act; when the maximum value of the
three line voltages are greater than the return value, the alarm
action will return.
Action characteristics: When the maximum voltage is less than
the action threshold (1), the alarm or trip delay will be activated;
At the end of the action delay time (2), an alarm or trip signal will
be issued, and the under voltage fault protection will act; When
the maximum voltage is greater than the return threshold (3), the
return delay will be activated; At the end of the return delay time
(4), the alarm will be removed and the under voltage fault protec-
tion will return.
Action threshold
Action delay time (s)
Return threshold (V)
Return delay time (s)
Action or alarm characteristics
(Delay tolerance ±10%)
Under-voltage alarm return characteristic
(Delay tolerance ±10%)
Alarm contact output
Over voltage Protection
The intelligent controller measures the RMS value of the primary
circuit voltage. When the three line voltages are all greater than
the set value, that is, when the minimum value of the three line
voltages is greater than the over voltage protection threshold, the
over voltage protection will act; when the three line voltages are
less than the return value, the alarm action will return.
Action characteristics: When the minimum voltage is greater than
the action threshold (1), the alarm or trip delay will be activated;
At the end of the action delay time (2), an alarm or trip signal will
be issued, and the over voltage fault protection will act; When the
execution mode is set as alarm, after the alarm action, the return
delay will be activated when the minimum voltage is less than the
return threshold (3); At the end of the return delay time (4), the
alarm will be removed and the over voltage fault protection will
return.
Action threshold
Action delay time (s)
Return threshold (V)
Return delay time (s)
Action or alarm characteristics
(Delay tolerance ±10%)
Over voltage alarm return characteristic
(Delay tolerance ±10%)
Alarm contact output
28
EATON www.eaton.com
100 ~ return threshold (Step is 1)
0.2 ~ 60 (Step is 0.1)
Action threshold ~ 1200 (Step is 1)
0.2 ~ 60 (Step is 0.1)
Umax / action threshold <0.9
Umax / action threshold 1.1
Umax / action threshold >1.1
Umax / action threshold 0.9
When the execution mode is alarm, the "under voltage alarm" contact output can be added
Return threshold - 1200 (Step is 1)
0.2 ~ 60 (Step is 0.1)
100 ~ Action threshold (Step is 1)
0.2 ~ 60 (Step is 0.1)
Umin / action threshold 1.1
Umin / action threshold <0.9
Umin / action threshold 0.9
Umin / action threshold >1.1
When the execution mode is alarm, the "over voltage alarm" contact output can be added
IZM6 Series Air Circuit Breaker
Under voltage protection acting principle
This set point is only available when the execution mode is
"Alarm", and the return value must be greater than or equal
to the start value.
Fixed time action or alarm
No action or alarm
Return
No return
Over voltage protection acting principle
This set point is only available when the execution mode is
"Alarm", and the return value must be greater than or equal to
the start value.
Fixed time action or alarm
No action or alarm
Return
No return
Operating Instruction Leafl et
1. Action threshold
2. Action delay time
3. Return threshold
4. Return delay time
1. Action threshold
2. Action delay time
3. Return threshold
4. Return delay time

Advertisement

Table of Contents
loading

This manual is also suitable for:

Izm65Izm67Izm69

Table of Contents