Raytech mini-ATOS Instruction Manual page 66

Mini automatic transformer observation system
Hide thumbs Also See for mini-ATOS:
Table of Contents

Advertisement

The warning symbol shows that it is not safe to touch the cables and test clamps
The actual point (the actual flux and the actual current) of the demagnetization curve
marked in green
The first point (initial remanence flux) of the demagnetization curve marked in red
The actual demagnetization current during the measurement
The actual flux during the measurement
The stop button can be used to stop the test. Please note that it takes time to discharge
and stop the test
WARNING!
After measurement stop, it takes time to discharge the test object!
Wait until the device mode changes to safe mode before any other
action!
90297-0.22 Instruction Manual mini-ATOS
Figure 60: Demagnetization view during the test
Page 66 of 92