11.3 AUXILIARY WATER DRIP TRAY FOR COLLECTING CONDENSATE FROM THE CONTROL VALVES
The auxiliary water drip tray is supplied with the base unit to-
gether with two fastening screws.
Its function is to collect the condensate generated by the control
valves and to convey it inside the main condensate drip tray of
the unit. (Fig.15 , Fig.16 )
» Fig15
1
Condensate discharge
11.4 CONNECTION FOR INTAKE OF FRESH AIR TO BE TREATED
The units are equipped with 3 fresh air inlets, positioned in the
corners. This air mixes with the air drawn in from the indoor en-
vironment and is then treated by the heat exchanger. (Fig.17 -
Fig.18 )
Ū The BAR accessory is available: a fitting for Ø100 pipe to be
connected to the inlets located on the unit.
Ū It is necessary to filter the fresh air before introducing it in
the unit, making sure that its temperature is not too low.
Ū To avoid operating and noise-related problems, the fresh air
flow rate is limited to 20% of the unit's air flow at average
speed, with a maximum of 110 m
WARNING: It is necessary to prevent the intake of dust and
impurities that could foul the unit's exchanger.
» AQ 10-20
3
/h for each intake.
All copying, even partial, of this manual is strictly forbidden
» Fig16
1
Condensate discharge
WARNING: The installation of the auxiliary water drip tray
is mandatory.
» AQ 40-50-60
WC66000496
45