Installation - Omron G3PX EUN Series Manual

Ac power controller
Table of Contents

Advertisement

G3PX

Installation

J TERMINAL ARRANGEMENT
G3PX-220EUN
G3PX-240EUN
G3PX-260EUN
1
External main setting
3 kΩB 2 W
MAN SET
2
Voltage ON/OFF input
VOLTAGE IN
3
Current input
4 to 20 mA DC CURRENT
4
(1 to 5 VDC)
(Voltage)
5
External duty setting
3 kΩB
6
MAN DUTY SET
7
SOURCE
8
9
100/110 VAC
50/60 Hz
10
Precautions
Note:
Open the terminals for 50 Hz or short-circuit the terminals for 60 Hz. When the product is shipped, the terminals are short-circuited
using a short-circuiting bar to set to 60 Hz. When using at 50 Hz, remove the short-circuiting bar.
J LOAD
Only resistive loads can be connected to the G3PX. Contact your
OMRON representatives if it is necessary to connect inductive or
transformer loads.
J MOUNTING
The three-phase, 60-A G3PX weighs approximately 5 kg. Pay ut-
most attention when mounting the G3PX so that the G3PX will not
fall thus resulting in injury.
Vertical Mounting
Note:
In the case of flat mounting, the 30% derating of the load
current is required.
2 kΩB, 2 W for
EUN-series models
5 to 24 VDC
INPUT
200/230 VAC
50/60 Hz
Flat Mounting
G3PX-220EC
G3PX-240EC
G3PX-260EC
CT UNIT
G32X-CT
1
W
11
2
B
12
3
13
RESET
4
14
5
15
ALARM
6
16
Internal
7
contact
configuration
17
8
18
OPEN 50 Hz
9
SHORT 60 Hz
19
(see note)
10
Close Mounting Example (Single-phase Models)
10 mm
10 mm
Note:
Make sure that there is a space of at least 50 mm
(1.97 in) vertically and at least 10 mm (0.39 in) hori-
zontally between adjacent single-phase models.
G3PX
External main setting
2 kΩB 2 W
MAN SET
Voltage ON/OFF input
VOLTAGE IN
Current input
4 to 20 mA DC CURRENT
(1 to 5 VDC)
5 to 24 VDC
(VOLTAGE)
INPUT
External duty setting
3 kΩB
MAN DUTY SET
SOURCE
200/230 VAC
50/60 Hz
100/110 VAC
50/60 Hz
10 mm
50 mm
10 mm