G3PX
The G3PX does not operate or is in abnormal operation.
Make sure that all input terminals are connected properly with no
mistakes in polarity.
Make sure that the internal DUTY adjuster is not set to the
farthest clockwise position.
Make sure that the frequency used by the G3PX (i.e., 50 or 60
Hz) is set properly. (This applies to the EC models.)
Temperature control with a Voltage-output Temperature
Controller is not smooth.
Make sure that the controlled soft-start up/down time has been
adjusted properly. If not, turn the TIME adjuster counterclockwise
to the minimum setting to reduce the controlled start-up/down
time.
Input signal
Controlled
soft-start
up
Input signal
Controlled
soft-start
up
The Level indicator is not OFF with a 0% input signal
(G3PX-2j0EUN Series).
Make sure that the BASE UP adjuster has been turned counter-
clockwise to the minimum setting.
Make sure that the adjuster
is turned counterclockwise
to the minimum setting.
BASE UP
The Level indicator LEDs of a constant-current model are all lit
and no power control operation is possible.
Make sure that the load current is large enough.
Remedy 1: Adjust the CUR LIM adjuster so that the LED on the
farthest right of the Level indicator is OFF.
TIME
Reduce this period.
TIME
Adjust so that this LED is OFF.
CUR LIM adjuster for limiting current
Remedy 2: When the supply current is less than 50%, increase
the number of turns of wire on the current transformer. When the
supply current is 50% of the rated current, the wires must be
coiled twice on the CT Unit. When the supply current is 25% of the
rated current, the wires must be coiled three to four times on the
CT Unit.
No reset will be performed even if the RESET button is
pressed. Check whether the RESET button is pressed while
there is nothing input into to power supply terminals 8 and 10
or 9 and 10 of the G3PX.
Be sure to press the RESET button with power supplied to the
G3PX.
The following wiring will be required if the breaker or contactor
connected between the power supply and the G3PX is operated
by the relay output of the G3PX.
Magnet
contactor
G3PX
Load