Download Print this page

Njoy Garun Series Installation Manual page 4

40 pieces battery cabinet
Hide thumbs Also See for Garun Series:

Advertisement

Step 5
Insert back the pieces that
hold the batteries in place.
Step 6
Find the connection cables. Each cable is numbered from 1 to 7, with the
following quantities for each cable type:
Nr.
Description
1
#10 AWG cable (Black)
2
#10 AWG cable (Black)
3
#10 AWG cable (Black)
4
#10 AWG cable (Red) - bound to the cabinet
5
#10 AWG cable (Black) - bound to the cabinet
6
#10 AWG cable (Blue) - bound to the cabinet
7
#10 AWG cable (Blue)
6
Front
of the
cabinet
Left side view
Cable numbering
Pieces
Cable numbering
32
1
2
2
2
3
2
4 (BAT+)
2
5 (BAT-)
2
6 (N)
2
7
Step 7
The following connections are made (according to the diagram on pages 8-9).
In the diagram each battery is coded according to tray level, side and number.
For example. DR2 means battery no. two (counting from the front of the
cabinet), from the Down tray, Right side of the cabinet:
7.1
Using cables no.1, connect all batteries on the 3 levels in series
((-, black) terminal of the first battery to the (+, red) terminal of the adjacent
battery), except for two batteries on the middle level, namely: MR3 and MR4,
respectively ML3 and ML4, which will be connected as shown in the step 7.6.
7.2
Using cables no.2 connect the free terminals of the ML7 batteries
with UL6, respectively, MR7 with UR6.
7.3
Using the cables no. 3, connect the free terminals of the DL1 batteries
with ML1, respectively MR1 with DR1.
7.4
Using one of the red no. 4 cables, bound to the cabinet, connect the
free (+, red) terminal of the DR7 battery on the right side of the cabinet. The
other red cable no. 4, bound to the cabinet, connect it to the free (+, red)
terminal of UL1 battery on the left side of the cabinet.
7.5
Using one of the no. 5, black cables, bounded to the cabinet, connect
the free (-, black) terminal of the UR1 battery on the right side of the cabinet.
The other black no. 5 cable, bounded to the cabinet, connect it to the free
(-, black) terminal of the DL7 battery on the left side of the cabinet.
7.6
Using the two blue short cables no.7, with one of the branch provided
with double connector, connect the free terminals of ML3 and ML4 batteries
on the left side, respectively MR3 and MR4 batteries on the right side. Then
connect the free terminals to one of the blue cables no. 6, bounded to the
cabinet (one on each side of the cabinet).
7

Advertisement

loading

This manual is also suitable for:

Upbpta1222ax-az01b