8-1. COOL (
/

) OPERATION

(1) Press OFF/ON (stop/operate) button.
OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select COOL mode with Operation select button.
(3) Press Temperature buttons (TEMP
The setting range is 61 ~ 88°F (16 ~ 31°C)
1. Coil frost prevention
When the temperature of indoor heat exchanger becomes too low, the coil frost prevention mode works.
The indoor fan operates at the set speed and the compressor stops. This mode continues until the temperature of indoor heat
exchanger rises.
2. Low outside temperature operation
When the outside temperature is lower, low outside temperature operation starts, and the outdoor fan slows or stops.
8-2. DRY (
/
) OPERATION
(1) Press OFF/ON (stop/operate) button.
OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select DRY mode with Operation select button.
(3) The set temperature is determined from the initial room temperature.
1. Coil frost prevention
Coil frost prevention is as same as COOL mode. (8-1.1.)
2. Low outside temperature operation
Low outside temperature operation is as same as COOL mode. (8-1.2.)
8-3. HEAT (
/
) OPERATION (MSZ)
(1) Press OFF/ON (stop/operate) button.
OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select HEAT mode with Operation select button.
(3) Press Temperature buttons (TEMP
The setting range is 61 ~ 88°F (16 ~ 31°C) (GS30/36NA)/50 ~ 88°F (10 ~ 31°C) (Other models).
1. Cold air prevention control
When the compressor is not operating or is starting, and the temperature of indoor heat exchanger and/or the room tempera-
ture is low or when defrosting is being done, the indoor fan will stop or rotate in Very Low speed.
2. High pressure protection
The compressor operational frequency is controlled by the temperature of the indoor heat exchanger to prevent the condens-
ing pressure from increasing excessively.
When the temperature of indoor heat exchanger becomes too high, the high pressure protection works.
The indoor fan operates following the cold air prevention control. This mode continues until the temperature of indoor heat
exchanger falls.
3. Defrosting
Defrosting starts when the temperature of outdoor heat exchanger becomes too low.
The compressor stops once, the indoor/outdoor fans stop, the 4-way valve reverses and the compressor re-starts.
This mode continues until the temperature of outdoor heat exchanger rises or the fixed time passes.
8-4. FAN (
/
) OPERATION (MSY)
(1) Press OFF/ON (stop/operate) button.
OPERATION INDICATOR lamp of the indoor unit turns ON with a beep tone.
(2) Select FAN mode with Operation select button.
(3) Select the desired fan speed. When AUTO, it becomes Low.
Only indoor fan operates. Outdoor unit does not operate.
8-5. "I FEEL CONTROL" (
(1) Press OFF/ON (stop/operate) button on the remote controller.
OPERATION INDICATOR lamp of the indoor unit turns on with a
beep tone.
(2) Select "I FEEL CONTROL" mode with Operation select button.
(3) The operation mode is determined by the room temperature at
start-up of the operation.
Once the mode is fixed, the mode does not change by room temperature afterwards.
Under the ON TIMER (
ation starts.
OBH874A
or
button/TOO WARM or TOO COOL button) to select the desired temperature.
or
button/TOO WARM or TOO COOL button) to select the desired temperature.
/
) OPERATION (MSY)
) operation, mode is determined according to the room temperature at the set time the oper-
Initial room temperature
77°F (25°C) or more
More than 55°F (13°C),
less than 77°F (25°C)
24
Mode
COOL mode of
"I FEEL CONTROL"
DRY mode of
"I FEEL CONTROL"