SPLIT-TYPE AIR CONDITIONERS
INSTALLATION MANUAL
1. BEFORE INSTALLATION
1-1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY
• Be sure to read these safety precautions and instructions.
• After reading this manual, be sure to store it with the OPERATING INSTRUCTIONS for future reference.
• Please report to your supply authority or obtain their consent before connecting this equipment to the power supply system.
■ Do not install the unit by yourself (user).
you purchased the unit.
■ Follow the instructions detailed in the installation manual.
or leakage of water.
■ When installing the unit, use appropriate protective equipment and tools for
safety.
Failure to do so could cause injury.
■ Install the unit securely in a place that can bear the weight of the unit.
If the installation location cannot bear the weight of the unit, the unit could fall causing
injury.
■ Do not alter the unit.
■ Perform electrical work according to the installation manual and be sure to use
an exclusive circuit. Do not connect other electrical appliances to the circuit.
■ Ground the unit correctly.
Do not connect the ground wire to a gas pipe, water pipe, lightning rod or telephone
ground. Defective grounding could cause electric shock.
■ Do not damage the wires.
■ Be sure to shut off the main power when setting up the indoor P.C. board or
wiring.
Failure to do so could cause electric shock.
If gas leaks and accumulates around the unit, it could cause an explosion.
■ Do not use intermediate connection of the power cord or the extension cord.
Do not connect many devices to one AC outlet.
electric shock, the unit falling, etc.
■ When plugging the power supply plug into the outlet, make sure that there is
no dust, blockage, or loose parts both in the outlet and on the plug. Verify that
the power supply plug is completely in the outlet.
If there is dust, blockage, or loose parts on the power supply plug or the outlet, it could
■ Depending on the installation area, install a Ground Fault Interrupt (GFI) circuit
breaker.
If the Ground Fault Interrupt (GFI) circuit breaker is not installed, an electric shock
could occur.
■ Perform the drainage/piping work securely according to the installation manual.
If there is defect in the drainage/piping work, water could drip from the unit, and
damage household items.
JG79N508H01
MSZ-GS24NA
MSY-GS24NA
When installing multi units, refer to the instal-
lation manual of the multi unit for outdoor unit
installation.
WARNING
-
CAUTION
Required Tools for Installation
Phillips screwdriver
Level
Scale
Utility knife or scissors
3 in. (75 mm) hole saw
Torque wrench
Wrench (or spanner)
(Could lead to death or serious injury.)
■ Securely attach the electrical cover to the indoor unit and the service panel to
the outdoor unit.
If the electrical cover of the indoor unit and/or the service panel of the outdoor unit are
an electric shock.
■ When installing, relocating, or servicing the unit, make sure that no substance
Any presence of foreign substance such as air can cause abnormal pressure rise and
for the system will cause mechanical failure, system malfunction, or unit breakdown.
In the worst case, this could lead to a serious impediment to securing product safety.
■ Do not discharge the refrigerant into the atmosphere. Check that the refrigerant gas
does not leak after installation has been completed. If refrigerant leaks during
installation, ventilate the room.
space heater, stove, etc., harmful gases will be generated.
■ Use appropriate tools and piping materials for installation.
The pressure of R410A is 1.6 times higher than R22. Not using the appropriate tools
and materials, or improper installation could cause the pipes to burst causing an injury.
■ When pumping down the refrigerant, stop the compressor before disconnecting
the refrigerant pipes.
If the refrigerant pipes are disconnected while the compressor is running and the
stop valve is open, air could be drawn in and the pressure in the refrigeration cycle
could become abnormally high, causing the pipes to burst.
■ When installing the unit, securely connect the refrigerant pipes before starting
the compressor.
If the compressor is started before the refrigerant pipes are connected and the stop
valve is open, air could be drawn in and the pressure in the refrigeration cycle could
become abnormally high, causing the pipes to burst.
■ Install the unit according to national wiring regulations.
■ When opening or closing the valve below freezing temperatures, refrigerant may
spurt out from the gap between the valve stem and the valve body, resulting in
injuries.
(Could lead to serious injury when operated incorrectly.)
This could cause injury.
■ Do not install the outdoor unit where small animals may live.
If small animals enter the unit and damage its electrical parts, it could cause a mal-
5/32 in. (4 mm) hexagonal wrench
Flare tool for R410A
Gauge manifold for R410A
Vacuum pump for R410A
Charge hose for R410A
Pipe cutter with reamer

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MSZ-GS24NA and is the answer not in the manual?

Questions and answers

Jeff Green
January 28, 2025

What is the dimension of the indoor mounting plate for MS Z gs24

1 comments:
Mr. Anderson
May 14, 2025

The indoor mounting plate dimensions for the Mitsubishi Electric MSZ-GS24NA are 8/5-41~4/3-31 and 6-7/8 inches.

This answer is automatically generated

Subscribe to Our Youtube Channel

Summary of Contents for Mitsubishi Electric MSZ-GS24NA

  • Page 1 Required Tools for Installation JG79N508H01 MSZ-GS24NA Phillips screwdriver 5/32 in. (4 mm) hexagonal wrench MSY-GS24NA Level Flare tool for R410A Scale Gauge manifold for R410A Utility knife or scissors Vacuum pump for R410A When installing multi units, refer to the instal- 3 in.
  • Page 2: Selecting The Installation Location

    Then, attach remote con- may cause chemical cracking. troller holder to a pillar or wall and install wireless remote controller. 1-3. SPECIFICATIONS 1-3-1. POWER SUPPLY AND INDOOR/OUTDOOR WIRE MSZ-GS24NA INDOOR CONNECTION MSY-GS24NA MODEL • Power should be taken from an exclusive branched circuit.
  • Page 3: Installation Diagram

    1-4. INSTALLATION DIAGRAM Wall hole cover (D) Use the wall hole sleeve Indoor unit (C) to prevent indoor/out- Seal the wall hole gap with putty (H). ACCESSORIES door connecting wire (A) Check the following parts before installation. from contacting metal parts Wall hole Attach the pipe to <Indoor unit>...
  • Page 4: Indoor Unit Installation

    2. INDOOR UNIT INSTALLATION 2-1. ATTACHING THE INSTALLATION PLATE Ceiling 2 1/8 in. (55 mm) or more 4 5/8 in. (118 mm) or more for left and left back piping (using spacer) • To prevent installation plate (1) from vibrating, be sure to install the attachment screws in Installation plate (1) Level the holes indicated in the illustration.
  • Page 5: Drain Piping

    2-4. PIPE FORMING AND DRAIN PIPING 2-4-1. PIPE FORMING • Place the drain hose below the refrigerant piping. • Make sure that the drain hose is not crowded or bent. Gas pipe Liquid pipe • Do not pull the hose when applying the tape. supplied).
  • Page 6: Outdoor Unit Installation

    3. OUTDOOR UNIT INSTALLATION 3-1. CONNECTING WIRES FOR OUTDOOR UNIT 1) Remove the service panel. 2) Remove the conduit cover. 3) Attach the conduit connectors to the conduit plate with lock nuts then secure it against unit with screws. 4) Connect the ground wires of indoor/outdoor unit connecting wire (A) and power supply 5/8 in.
  • Page 7: Purging Procedures, Leak Test, And Test Run

    4. PURGING PROCEDURES, LEAK TEST, AND TEST RUN 4-1. PURGING PROCEDURES AND LEAK TEST 4-2. TEST RUN 1) Remove service port caps from stop valves on both sides of refrigerant lines. (The stop 1) Insert power supply plug into the power outlet and/or turn on the breaker.
  • Page 8: Pumping Down

    5-2. REMOVING THE INDOOR UNIT Remove the bottom of the indoor unit from the installation plate. When releasing the corner part, release both left and right bottom corner part of indoor unit If the above method cannot be used Remove the panel. Then, insert hexagonal wrenches into the square holes on the left and indoor unit lowers and releases the hooks.