Piping Installation; Preparing Refrigerant Piping; Refrigerant Piping Requirements - Daikin FHA35AVEB98 Installation And Operation Manual

Hide thumbs Also See for FHA35AVEB98:
Table of Contents

Advertisement

a
b
c
d
e
f
a
Round part
b
Rectangular part of the decoration side panel
c
Decoration side panel
d
Screw
e
Reinforcing plate
f
Right drain piping
Drain piping connection
1
2~5
c
a
b
1
A
d c b
a
Drain pipe connection (attached to the unit)
b
Drain hose (accessory)
c
Metal clamp (accessory)
d
Large sealing pad (accessory)
e
Drain piping (field supply)
f
Tightened part of metal clamp
A
In case of bending the end of the metal clamp
B
In case of wrapping the end of the metal clamp with vinyl
tape
1 Push the drain hose as far as possible over the drain pipe
connection.
2 Tighten the metal clamp at the base of the drain socket. Wrap
the end of the metal clamp with vinyl tape or bend the end
inwards to avoid damaging the sealing pad.
3 Check for water leaks (see
4 Wind the large sealing pad (= insulation) around the metal
clamp and drain hose, and fix it with tie wraps. Start wrapping
from the tightened part of the metal clamp so that the end of the
metal clamp is wrapped twice.
5 Connect the drain piping to the drain hose.
To check for water leaks
Make sure the unit is level in accordance with the instructions in
"12.2.1  Guidelines when installing the indoor
pour approximately 1 l of water through the air discharge outlet, and
check for leaks.
FHA-A(9)
Split system air conditioner
3P668115-4E – 2022.11
d
e
2
3
4
5
A
A
A'
A'
A-A'
A-A'
B
f
d c b
f
leaks" [ 4  17]).
"To check for water
unit"  [ 4   14]. Gradually
a
b
a
Air outlet
b
Plastic water container with tube length ≥100 mm
13

Piping installation

13.1

Preparing refrigerant piping

13.1.1

Refrigerant piping requirements

CAUTION
Piping MUST be installed according to instructions given in
"13  Piping
installation"  [ 4   17]. Only mechanical joints (e.g.
braze+flare connections) that are compliant with the latest
version of ISO14903 can be used.
NOTICE
The piping and other pressure-containing parts shall be
suitable for refrigerant. Use phosphoric acid deoxidised
seamless copper for refrigerant piping.
▪ Foreign materials inside pipes (including oils for fabrication) must
be ≤30 mg/10 m.
Refrigerant piping diameter
For piping connection of the indoor unit, use the following piping
diameters:
Class
Liquid pipe
35
50+60
71~140
Refrigerant piping material
▪ Piping material: phosphoric acid deoxidised seamless copper
▪ Flare connections: Only use annealed material.
▪ Piping temper grade and thickness:
Outer diameter
Temper grade
(Ø)
6.4 mm (1/4")
Annealed (O)
9.5 mm (3/8")
12.7 mm (1/2")
15.9 mm (5/8")
(a)
Depending on the applicable legislation and the maximum
working pressure of the unit (see "PS High" on the unit name
plate), larger piping thickness might be required.
13 Piping installation
(mm)
Pipe outer diameter (mm)
Gas pipe
Ø6.4
Ø9.5
Ø6.4
Ø12.7
Ø9.5
Ø15.9
(a)
Thickness (t)
Ø
≥0.8 mm
Installation and operation manual
t
17