RYMASKON
400 - Modbus
RYMASKON
®
stands for a series of multifunctional room control units. The individually configurable RYMASKON
monitoring and control of the indoor climate and illumination in a Modbus network. It has two digital inputs and two digital/analogue outputs. Room
climate control and regulation can be accessed from a central point on a higher-level Modbus master and on-site operation can be selectively
or completely disabled. Thanks to its internal outputs, the inputs and settings on the device do not necessarily have to be processed by the master.
This means that it is also possible to have decentralised individual room control at any time. An internal sensor detects the room temperature.
Six freely assignable function buttons on the front panel of the unit can be used for on-site operation and configuration. An integrated rotary encoder
with a central input button enables manual adjustment of settings and parameter assignment on location. Desired functions (such as "Light ON") and
display values can be activated by triggering an approximation sensor when entering the room. The dimmable multifunctional display is designed
specifically for room operation and uses intuitive symbols for a clear view of all available spatial data. Besides the time, weekday and climate
parameters (temperature, humidity, dew point, CO
open, lighting, alarm, key lock or room occupancy.
TECHNICAL DATA
Power supply:
Power consumption:
Inputs:
Outputs:
Interface:
Sensor:
Operating elements:
Electrical connection:
Enclosure:
Dimensions:
Mounting:
Ambient temperature:
Permitted humidity:
Protection type:
Standards:
RYMASKON
®
400 - Modbus – Room control unit for room automation
Type ⁄ WG 02
®
RYMASKON
410 - Modbus
RYMASKON 411
RYMASKON 412
®
RYMASKON
420 - Modbus
RYMASKON 421
RYMASKON 422
content), it can also display additional features, such as heating/cooling and fan modes, window
2
24 V DC (± 10 %)
1.08 W at 100 % backlighting
0.94 W at 15 % backlighting
0.89 W without backlighting
(without load at the actuator outputs)
2 digital inputs
without additional 0 V output signal *
RYMASKON 410 : 2 analogue outputs (0-10 V DC)
rated current max. 4 mA
RYMASKON 420 : 2 digital outputs or PWM
rated current 400 mA (short circuit max. 1.2 A)
RS485 Modbus RTU Slave (57600, 38400, 19200, 9600 Baud),
bus termination can be set via DIP switch
NTC 10 kΩ, 0...+70 °C, precision ±0.4 K
multifunctional display, 6 touch buttons, 1 rotary encoder, 1 approximation sensor (IR)
0.14 - 1.5 mm², via plug-in screw terminals
plastic, glass front panel, black or white colour
88 x 173 x 30 mm (incl. connection terminals)
using a plastic mounting plate (see dimensional drawing),
wall mounting or on in-wall flush double switch box
+5...+40 °C (operation); –10...+50 °C (storage)
0...85 % r. H. (without dew formation)
IP 20 (according to EN 60 529)
CE-conformity, electromagnetic compatibility according to EN 61 326,
EMC Directive 2014 ⁄ 30 ⁄ EU
Communication
Output
RS485
2x (analogue) 0-10V
RS485
2x (analogue) 0-10V
RS485
2x (digital / PWM)
RS485
2x (digital / PWM)
PWM = pulse-width modulation
®
400 - Modbus enables automated
Colour
Display
Item No.
black
1901- 5121- 2101-000
white
1901- 5121- 2102-000
black
1901- 5121- 2201-000
white
1901- 5121- 2202-000
Rev. 0000 - V10 GB

Advertisement

loading

Summary of Contents for S+S Regeltechnik RYMASKON 400-Modbus

  • Page 1 ® RYMASKON 400 - Modbus Rev. 0000 - V10 GB RYMASKON ® stands for a series of multifunctional room control units. The individually configurable RYMASKON ® 400 - Modbus enables automated monitoring and control of the indoor climate and illumination in a Modbus network. It has two digital inputs and two digital/analogue outputs. Room climate control and regulation can be accessed from a central point on a higher-level Modbus master and on-site operation can be selectively or completely disabled.
  • Page 2 ® RYMASKON 400 - Modbus Rev. 0000 - V10 GB ® ® Schematic diagram * RYMASKON 410 - Modbus Connecting RYMASKON 410 - Modbus diagram RYMASKON 410 MOD1+ Input 1 DI-1 (digital) 0 V MOD1– Input 2 DI-2 (digital) 0 V +UB 24V /1 Output 1 AO-1 (analogue) 0-10 V DC...
  • Page 3 ® RYMASKON 400 - Modbus | Installation and configuration Installation The device is attached to the mounting frame, which is mounted onto a local dual device junction box. The device front panel is then attached to the mounting frame by means of the upper and lower retaining clips. Putting into operation ®...

This manual is also suitable for:

Rymaskon 401-modbusRymaskon 420-modbusRymaskon 411Rymaskon 412Rymaskon 421Rymaskon 422 ... Show all