S+S Regeltechnik RYMASKON 200-Modbus User Manual page 25

Modbus slave, room control units
Hide thumbs Also See for RYMASKON 200-Modbus:
Table of Contents

Advertisement

®
RYMASKON
200-Modbus
Modbus Slave User Manual
Register Name
direct_value
direct_value_config
Table 15: Direct Value
Register Name
system_time
Table 16: System Time
© S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470
Register
Address
15
14
13
104
0x0068
105
EN
R
R
[0]
[0]
[0]
0x0069
These registers are used to display specific values instead of display_values or set_points. For an
overview on how to setup the configuration please refer to Figure 7 on Page 18.
direct_value: 16 bit signed integer to be displayed
EN: direct value enable bit (1 – enabled, 0 – disabled)
unit: defines a unit symbol to be displayed, following values are possible:
0x0 0x1 0x2 0x3 0x4
no
°C
unit
exp: exponent, defines the number of decimal places:
00 – no decimal point
01 – one decimal place
10 – two decimal places
11 – three deciml places
!!! If disabled, the last viewed value will be visible again as defined with the
user_interface_direct_access register at adderss 101 (Table 13 on Page 23).
Register
Address
15
14
13
112
0x0070
113
0x0071
system_time represent a 32 bit timestamp in seconds since JAN-01-1970. The timestamp has to be
initially set by the Modbus master because the device has no back-up battery and so it would start at 0
(00:00:00 JAN-01-1970) after a reboot.
The timestamp is incremented by the device but anyway it has to be set by the master at defined intervals
to prevent time offsets.
Bit Position
12
11
10
9
8
[0x0000]
R
R
R
R
R
[0]
[0]
[0]
[0]
[0]
0x5
0x6
°F
cfm
l/s
m³/h
Pa
Bit Position
12
11
10
9
8
system_time_0
[0x0000]
system_time_1
[0x0000]
Page 25 of 55
7
6
5
4
3
unit
R
R
[0]
[0]
[0x0]
0x7
0x8 0x9
0xA
inWC
V
%
%RH ppm
7
6
5
4
3
2
1
0
exp
[00]
0xB
2
1
0
|www.SplusS.de