S+S Regeltechnik RYMASKON 200-Modbus User Manual page 28

Modbus slave, room control units
Hide thumbs Also See for RYMASKON 200-Modbus:
Table of Contents

Advertisement

®
RYMASKON
200-Modbus
Modbus Slave User Manual
Register Name
lcd_color_red
lcd_color_green
lcd_color_blue
lcd_brightness_contrast
user_interface_settings
Table 20: User Interface Settings
© S+S REGELTECHNIK GMBH | THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470
Register
Address
15
14
13
179
0x00B3
180
0x00B4
181
0x00B5
182
lcd_contrast
0x00B6
183
DAD
0x00B7
[0x0]
These registers are used to configure basic features of the display and the button interface.
color_brightness:
defines the brightness of a specific backlight color.
Values from 0x00 – 0% to 0x64 – 100% are valid.
lcd_brightness:
defines the overall brightness of the LCD backlight.
Values from 0x00 – 0% to 0x64 – 100% are valid.
lcd_contrast:
defines the contrast setting of the LCD.
Values from 0x00 – 0% to 0x64 – 100% are valid.
lcd_color_scheme:
sets a predefined color setting, possible values are:
0x0 – user (as defined with the above values)
0x1 – white
0x2 – red
0x3 – green
0x4 – blue
0x5 – orange
0x6 – magenta
0x7 – cyan
DAS:
display auto shuffle mode (0 – off, 1 – on), display values and set points will
be shuffled after a defined timeout of 1 minute, each value is shown for 5
seconds
TF:
time format (0 – 12h, 1 – 24h), if TF is set to 12h the date format will also be
set to MM/DD instead of DD/MM
Date:
show date in secondary display (0 – off, 1 – on)
Time:
show time in secondary display (0 – off, 1 – on)
AF:
acoustic feedback for touch buttons (0 – off, 1 – on)
GFV:
goto first value after a defined timeout of 1 minute (0 – off, 1 – on)
DAD:
display auto dim, dim display brightness after 2 minutes to following defined
values:
0x0 – off (disabled)
0x1 – 50% lcd_brightness
0x2 – 10% lcd_brightness
0x3 – 0% lcd_brightness
0x4 – 0% lcd_brightness
!!! Compare Table 4 on Page 15 for device settings editable via the user interface.
Bit Position
12
11
10
9
8
reserved
[0x00]
reserved
[0x00]
reserved
[0x00]
[0x64]
GFV
AF
Time
Date
TF
[1]
[1]
[1]
[0]
[1]
Page 28 of 55
7
6
5
4
3
color_brightness
[0x64]
color_brightness
[0x64]
color_brightness
[0x64]
lcd_brightness
[0x64]
lcd_color_scheme
DAS
R
[0]
[0]
[0x0]
2
1
0
|www.SplusS.de

Advertisement

Table of Contents
loading

Table of Contents