5.2.1

Triggering of a diagnostics interrupt

Triggering of a diagnostics interrupt
For an incoming or outgoing event (e.g. wire break on a channel of an I/O module), the
module triggers a diagnostics interrupt if this is configured accordingly.
The CPU interrupts the processing of the user program and processes the diagnostics
interrupt OB (OB 82). The event that triggered the interrupt is entered in the start
information of the diagnostics interrupt OB.
5.2.2

Triggering a hardware interrupt

Triggering a hardware interrupt
In the event of a hardware interrupt, the CPU interrupts processing of the user program and
processes the process interrupt OB, e.g. OB 40. The event that triggered the interrupt is
entered in the start information of the hardware interrupt OB.
Note
Diagnostics "Hardware interrupt lost" (from I/O module)
Do not use hardware interrupts for functional purposes (e.g. cyclic generation of hardware
interrupts).
If the hardware interrupt load is too high, hardware interrupts can get lost depending on the
number of I/O modules and the communication load.
Interface Module IM 155-6 PN R1 (6ES7155-6AU00-0HM0)
Equipment Manual, 11/2022, A5E51160307-AA
Interrupts, error messages, diagnostics and system alarms
5.2 Interrupts