4 Electrical Connections

Terminal Block 1
Number
Marking
1
2
3
4
5
Terminal Block 2
Number
Marking
1
2
3
4
5
6
7
Note: OELD is reverse polarity protected.
Spare conductors must be terminated in a spare terminal. Wiring must be in accordance with local,
national and/or company regulations. Bare conductors must be avoided.
Refer to individual sensor manuals for sensor wiring details. Specific wiring diagrams for some com-
monly used sensors are provided in the Appendix.
The mA loop voltage is Max 32 VDC and current is Max 22 mA.
Color
Description
V+
Red
V+ Field Power
V-
Black
V- Field Power
mA
White
mA Signal to Field Wiring
V+
Red
Reserved for Excel Cross-duct Heater
V-
Black
Reserved for Excel Cross-duct Heater
Color
Description
V+
Red
V+ Sensor Power
V-
Black
V- Sensor Power
mA
White
mA Signal to Sensor
485A
Blue
RS485+ to Sensor
485B
Orange
RS485- to Sensor
485A
Blue
Reserved for SHC-1
485B
Orange
Reserved for SHC-1