2 ANALOG INPUT MODULE, MULTIPLE INPUT MODULE FB
18
2.3 M+Model_SetLoggingParam (Logging function setting)
Name
Data type
Logging cycle setting
Word [Unsigned]/Bit
value
String [16-bit]
Logging cycle unit
Word [Unsigned]/Bit
setting
String [16-bit]
Number of
Word [Unsigned]/Bit
posttrigger logging
String [16-bit]
points
Level trigger
Word [Unsigned]/Bit
condition setting
String [16-bit]
Trigger data
Word [Unsigned]/Bit
String [16-bit]
Trigger setting value
Word [Signed]
Module type
Word [Unsigned]/Bit
String [16-bit]
Name
Data type
Execution status
Bit
Normal completion
Bit
Error completion
Bit
Error code
Word [Unsigned]/Bit
String [16-bit]
Range
Description
Sets the interval of cycles at which data is stored.
■FX5-4AD
When the logging
cycle unit setting is 0:
80 to 32767
When the logging
cycle unit setting is 1:
1 to 32767
When the logging
cycle unit setting is 2:
1 to 3600
■FX5-8AD
When the logging
cycle unit setting is 1
(current/voltage
range): 1 to 32767
When the logging
cycle unit setting is 1
(resistance
temperature
detector/
thermocouple
range): 40 to 32767
When the logging
cycle unit setting is 2:
1 to 3600
Specifies the unit of cycles at which data is stored.
■FX5-4AD
0: s
1: ms
2: s
■FX5-8AD
1: ms
2: s
1 to 10000
Specifies the number of data to be logged after a hold
trigger occurs by one point.
0: Disable
Sets the condition in which a level trigger is to be used.
1: Rise
Set 0 if using no lever trigger.
2: Fall
3: Rise and fall
0 to 9999
Specifies a buffer memory address to be monitored by
level trigger.
-32768 to +32767
Sets the level at which a level trigger is generated.
Specifies a module type.
■FX5-4AD
0: FX5-4AD
■FX5-8AD
0: FX5-8AD
Default value
Description
OFF
ON: The execution command is ON.
OFF: The execution command is OFF.
OFF
The on state indicates that the setting of the logging
function parameters is completed.
OFF
The on state indicates that an error has occurred in the
FB.
0
The error code of an error occurred in the FB is stored.