All documentation relating to DIRIS Digiware and its associated sensors is available on the SOCOMEC website at the following address: www.socomec.com/en/diris-digiware Related instruction manuals Additional instruction manuals linked to the DIRIS Digiware system can be found on the Socomec website: Instruction manual Reference Easy Config System - Configuration Software...
• The auxiliary power supply voltage indicated on the device is observed: 24 VDC ± 10%. • The use of a SOCOMEC 230 VAC / 24 VDC power unit or a 24 VDC max 20 W class 2 power unit / SELV according to UL1310.
Before commissioning your DIRIS Digiware system, make sure all equipment operate under the latest firmware versions. The latest firmware versions are available on the Socomec website. The firmware upgrade is done using the Product Upgrade Tool software, by connecting a laptop to the Micro USB port of your DIRIS Digiware equipment.
Thanks to its architecture, DIRIS Digiware can be easily integrated into an energy management system which requires a large number of loads to be monitored. * PMD: Power Metering and Monitoring Device in accordance with IEC 61557-12. DIRIS Digiware - 542875G - SOCOMEC...
5.1.2. Principle DIRIS Digiware U DIRIS Digiware I Voltage measurement Current inputs (3I) Multipoint display DIRIS Digiware D Communication gateway DIRIS Digiware M DIRIS Digiware - 542875G - SOCOMEC...
Page 13
DIRIS Digiware S DIRIS Digiware I DIRIS Digiware I Current inputs (4I) DIRIS Current Digiware IO inputs (6I) Inputs/ outputs Current sensors TE, TR/iTR or TF DIRIS Digiware - 542875G - SOCOMEC...
DIRIS Digiware D-70 display - Time synchronisation done by the DIRIS Digiware M-50/M-70 gateway and DIRIS Digiware D-50/D-70 display - Auto-Discovery of slave modules from the DIRIS Digiware M gateway and DIRIS Digiware D display DIRIS Digiware - 542875G - SOCOMEC...
Voltage dips, swells and interruptions according to EN50160 • Alarms Thresholds • Data logging Trends of average values • Format Width/Number of modules 18 mm / 1 18 mm / 1 18 mm / 1 Part number 4829 0105 4829 0106 4829 0102 DIRIS Digiware - 542875G - SOCOMEC...
Page 17
DIRIS Digiware IO IO-10 IO-20 Application Metering / Monitoring / Analysis Number of digital inputs/outputs Number of analogue inputs Format Width 18 mm 18 mm Number of modules Part number 4829 0140 4829 0145 DIRIS Digiware - 542875G - SOCOMEC...
TE / TR/iTR / TF TE / TR/iTR / TF For connecting the current sensors, use SOCOMEC cables or RJ12 straight cables, twisted pair, unshielded, 600 V -10°C / +70°C. It is recommended that all the current sensors be installed in the same direction.
Maximum l Part number 4829 0500 4829 0501 4829 0502 4829 0503 4829 0504 4829 0505 TE-90 Pitch 90 mm Nominal current range In 600 - 2000 A Maximum l 2400 A Part number 4829 0506 DIRIS Digiware - 542875G - SOCOMEC...
5A adaptor 5 A I nom. 6 A I max. 4829 0599 Part number 5.2.4.2. Dimensions Dimensions in/mm 5A adapter 1.10 x 0.79 x 1.77 LxHxD 28 x 20 x 45 Ø 0.33 Aperture (W) Ø 8.4 DIRIS Digiware - 542875G - SOCOMEC...
0.29 or 0.59 in 7.5 or 15 mm 6.2.2. DIRIS Digiware C, U, I-3x, I-6x, IO-x - backplate-mounting 0.19 in 5 mm Type of screw: M4 Tightening torque: 0.5 Nm Washer diameter 0.47 in / 12 mm max. DIRIS Digiware - 542875G - SOCOMEC...
Position I Position II 6.2.4. DIRIS Digiware I-4x - back-plate mounting Mounting of the brackets on the top and bottom Type of screw: M4 of the Tightening torque: 0.5 Nm module. Washer diameter 0.47 in / 12 mm max. DIRIS Digiware - 542875G - SOCOMEC...
Step 1: Insert the tool through one of the current inputs and into the corresponding breaker terminal. Step 2: Tighten the associated screw(s). Please refer to the operating instructions of the protective device for additional information related to its installation. Ref: 4829 0196 (x10) DIRIS Digiware - 542875G - SOCOMEC...
The dimensions of the tightening clamp must not exceed 4 mm x 2 mm. 6.2.8. Accessories overview Part number Description 4829 0195 DIN-rail and back plate fixing tool (x10) 48290196 Temporary MCB insert (x10) DIRIS Digiware - 542875G - SOCOMEC...
4829 0501 4829 0502 TE-25 25 mm 4829 0503 TE-35 35 mm 4829 0504 TE-45 45 mm 4829 0505 TE-55 55 mm 4829 0506 TE-90 90 mm 6.3.2. DIN rail mounting TE-18 -> TE-55 DIRIS Digiware - 542875G - SOCOMEC...
Page 31
Note: it is possible to fix the TE-90 sensor to a DIN rail to make it easier to install. This is a temporary installation. Remove the clamps to install the TE-90 sensors on the DIN rail. DIRIS Digiware - 542875G - SOCOMEC...
Page 33
TE-90 Removing the clamps Ø 0.20 Ø 5.2 Note: remove the clamps to install the TE-90 sensors on the back-plate. DIRIS Digiware - 542875G - SOCOMEC...
Note: remove the clamps to install the TE-90 sensors on a cable with clamping collar. Do NOT clamp or pull out NON-INSULATED conductors carrying DANGEROUS VOLTAGE which could cause an electric shock, burn or arc flash. Ref. IEC 61010-2-032 DIRIS Digiware - 542875G - SOCOMEC...
The jaws must be perpendicular to the holding notches. Do NOT clamp or pull out NON-INSULATED conductors carrying DANGEROUS VOLTAGE which could cause an electric shock, burn or arc flash. Ref. IEC 61010-2-032 DIRIS Digiware - 542875G - SOCOMEC...
Mounting accessories for sensor combination: Part number Linear assembly Staggered assembly 4829 0598 These accessories must be ordered separately. 6.3.7. Sealing accessories for sensors Sealing case for terminal Part number 4829 0600 These accessories must be ordered separately. DIRIS Digiware - 542875G - SOCOMEC...
Do NOT clamp or pull out NON-INSULATED conductors carrying DANGEROUS VOLTAGE which could cause an electric shock, burn or arc flash. Ref. IEC 61010-2-032. Before closing the TR /iTR sensor, check that the air gap is clean (no contamination or corrosion). DIRIS Digiware - 542875G - SOCOMEC...
Centred position for the best measurement Do NOT clamp or pull out NON- INSULATED conductors carrying DANGEROUS VOLTAGE which could cause an electric shock, Centred position for the best burn or arc flash. measurement Ref. IEC 61010-2-032 DIRIS Digiware - 542875G - SOCOMEC...
6.6. Installing the 5A adapter 5A secondary current transformer Do NOT clamp or pull out NON-INSULATED conductors carrying DANGEROUS VOLTAGE which could cause an electric shock, burn or arc flash. Ref. IEC 61010-2-032. DIRIS Digiware - 542875G - SOCOMEC...
0.14 mm -> 1.5 mm flexible 7 mm Use Copper conductors only RS485 line polarisation Current sensors OFF = RS485 line polarisation TE, TR/iTR or TF disabled (by default) ON = RS485 line polarisation enabled DIRIS Digiware - 542875G - SOCOMEC...
Page 41
Only use a SOCOMEC Digiware bus cable (UTP RJ45 straight, twisted pair, unshielded, AWG24, 600V CAT V (-10 ... +70°C). When wiring, make sure you separate the low voltage (LV) section and the very low voltage (SELV) section to prevent any risk of electric shock.
Page 42
Protection 1A gG Protection 1A gG (*) The use of a 1A / 24 VDC fuse protection is recommended if the 24 VDC power supply is not provided by Socomec. For North America, the use of recognized fuses is mandatory.
TE / TR/iTR / TF TE / TR/iTR / TF TE / TR/iTR / TF - For connecting the current sensors, only use a SOCOMEC RJ12 cables (UTP unshielded, twisted pair, straight, AWG24, 600V, CATV, -10 ... +70°C). - Always connect input I01 first.
1, 2, 3 or 4 sensors for balanced or unbalanced loads. The overall accuracy of the measurement chain (DIRIS Digiware + sensors) is guaranteed. To guarantee this accuracy, SOCOMEC current sensor connection cables or equivalent must be used. 7.3.1. Configurable loads based on the network type...
Page 45
Fuse: 0.5 A gG / BS 88 2A gG / 0.5 A class CC Listed fuses for UL application. V1 V2 V3 VN V1 V2 V3 VN V1 V2 V3 VN V1 V2 V3 VN V1 V2 V3 VN V1 V2 V3 VN V1 V2 V3 VN DIRIS Digiware - 542875G - SOCOMEC...
Page 46
V1 V2 V3 VN V1 V2 V3 VN V1 V2 Fuse: 0.5 A gG / BS 88 2A gG / 0.5 A class CC Listed fuses for UL application. V1 V2 V3 VN V1 V2 V3 VN DIRIS Digiware - 542875G - SOCOMEC...
It is recommended that the functional earth be connected to guarantee optimum measurement accuracy and better emissivity/immunity for the electromagnetic compatibility (class B in conducted emission). In order to use the VirtualMonitor and AutoCorrect technologies, Earth must be connected to the DIRIS Digiware U module. DIRIS Digiware - 542875G - SOCOMEC...
50 m reel + 100 connectors 4829 0185 Use the shortest possible length of cable to optimise the electromagnetic emissions. The total maximum length must not exceed 100 metres. Use only SOCOMEC RJ45 cables for the Digiware bus. DIRIS Digiware - 542875G - SOCOMEC...
Socomec has estimated (but this can vary from one connector to another) that the power loss of an RJ45 female/ female connector averages 0.1 W and represents an additional 3.33m of RJ45 cable length within the Digiware bus.
24 VDC 24 VDC I-4x I-4x power supply power supply The DIRIS Digiware U voltage module must be located upstream of the repeater. The repeater has a 24VDC power supply. DIRIS Digiware C-32 24VDC DIRIS Digiware - 542875G - SOCOMEC...
The voltage detection feature is an indication of the presence or the absence of voltage on one of the phases. It should only be used as an indication, and must not replace the use of a voltage tester. In addition, the nominal voltage must be correctly configured in the DIRIS Digiware U module DIRIS Digiware - 542875G - SOCOMEC...
- FAST (default mode): this mode will only detect DIRIS Digiware modules on the Digiware bus and RS485 bus, DIRIS B and DIRIS A-40 on the RS485 bus. - FULL: this mode will also detect other Socomec PMDs (DIRIS A) and meters (COUNTIS E) connected on the RS485 bus.
Page 57
If you would like to assign specific Modbus addresses to the devices connected to the M-50/M-70 gateway, launch the auto-discovery from the Easy Config System software, and change the Modbus addresses of slave devices directly from the dashboard of the M-50/M-70 gateway (see 13.2). DIRIS Digiware - 542875G - SOCOMEC...
6. The auto-discovery process is finished, the D-xx display shows the number of discovered devices (3 in our example). The COM LEDs blink when communication is on-going between the D-xx display and downstream modules. DIRIS Digiware - 542875G - SOCOMEC...
- A 120 Ω resistor must be added at the start of the RS485 link - A 120 Ω resistor must be added at the end of the RS485 link - A terminating resistor must be added at the end of the Digiware bus. DIRIS Digiware - 542875G - SOCOMEC...
- An end of line resistor must be added at the end of the Digiware bus. 11.5. Communication tables The communication tables and associated explanations can be found on the documentations page for DIRIS Digiware on the SOCOMEC website: www.socomec.com/operating-instructions_en.html DIRIS Digiware - 542875G - SOCOMEC...
Config System must be installed before using the USB connection. Before configuring the DIRIS Digiware system, please make sure it operates using the latest available firmware versions. The latest firmware versions are available on the Socomec website. 12.1. Connection modes >...
The main settings of the DIRIS Digiware system (U, S, I, IO) can be configured from the DIRIS Digiware D-xx display directly. Refer to the manual for the DIRIS Digiware D display for more details. DIRIS Digiware - 542875G - SOCOMEC...
- Via a digital input (for devices with digital inputs, such as DIRIS Digiware IO-10 and I-4x modules) Output report System alarms can be linked to a digital output for alarm reporting purposes. Delay A time delay can be configured at the start and the end of the alarm. DIRIS Digiware - 542875G - SOCOMEC...
- Via a digital input (for devices with digital inputs, such as DIRIS Digiware IO-10 and I-4x modules) Output report Protection alarms can be linked to a digital output for alarm reporting purposes. Delay A time delay can be configured at the start and the end of the alarm. DIRIS Digiware - 542875G - SOCOMEC...
- Via a digital input (for devices with digital inputs, such as IO-10, I-4x etc.) Output report Logical alarms can be linked to a digital output for alarm reporting purposes. Delay A time delay can be configured at the start and the end of the alarm. DIRIS Digiware - 542875G - SOCOMEC...
- Via a digital input (for devices with digital inputs, such as DIRIS Digiware I-4x) Output report The overcurrent alarm can be linked to a digital output for alarm reporting purposes. Delay A time delay can be configured at the start and the end of the alarm. DIRIS Digiware - 542875G - SOCOMEC...
Visualisation is available from the DIRIS Digiware D-50/D-70 displays and WEBVIEW, embedded in the DIRIS Digiware M-70/D-70 and DATALOG H80/H81. You must configure the type of protective device from the Easy Config System software in the “Protection” menu for the VirtualMonitor function to be used: DIRIS Digiware - 542875G - SOCOMEC...
Page 68
An example corresponding to the above illustration is given in the table below: Voltage measured on U module ? Yes, 230V L-N Voltage detected on S modules ? No, 0V Position of protective device Closed Open Closed DIRIS Digiware - 542875G - SOCOMEC...
Page 69
For the voltage detection (hence the VirtualMonitor technology) to work properly when using iTR current sensors, make sure the section of live conductors are above the minimal sections given in the table below: iTR Type iTR-10 iTR-14 iTR-21 iTR-32 Min cable section (mm²) DIRIS Digiware - 542875G - SOCOMEC...
Ex.1: DIRIS Digiware I module and iTR current sensors, with phase inversion of current sensors 1 and 3. Let’s consider a phase inversion between current sensors 1 and 3, as showed in the following picture: DIRIS Digiware - 542875G - SOCOMEC...
Page 71
POSITIVE • Now the wiring has been corrected in the software and power values are correctly calculated: >> AUTOCORRECT PC 1-2-3 INPUT +/DIRECT +/DIRECT +/DIRECT PRESS OK TO LAUNCH AUTOCORRECT DIRIS Digiware - 542875G - SOCOMEC...
Page 72
• Press “OK” to launch AUTOCORRECT, and choose a positive power sign. The error mark is cleared and the cell WAY is no longer gray: >> AUTOCORRECT PC 1-2-3 INPUT -/INV +/DIRECT +/DIRECT PRESS OK TO LAUNCH AUTOCORRECT DIRIS Digiware - 542875G - SOCOMEC...
If inconsistencies are detected, cells will be highlighted in red and an automatic software correction is possible by clicking on "AutoCorrect". DIRIS Digiware - 542875G - SOCOMEC...
Page 74
After clicking on "AutoCorrect" the association errors are corrected and there are no more red cells in the diagnostic table: You can also correct the wrong voltage/current association manually in the "Current Sensors" menu: DIRIS Digiware - 542875G - SOCOMEC...
Page 75
For the voltage detection (hence the AutoCorrect technology) to work properly, make sure the section of live conductors are above the minimal sections given in the table below: iTR Type iTR-10 iTR-14 iTR-21 iTR-32 Min cable section (mm²) DIRIS Digiware - 542875G - SOCOMEC...
Network type Single-phase/ Two-phase / Two-phase with neutral / Three-phase / Three-phase with neutral Measurement by voltage transformer Primary: 400,000 VAC Secondary: 60, 100, 110, 173, 190 VAC Input consumption ≤ 0.1 VA Permanent overload 300 VAC Ph/N DIRIS Digiware - 542875G - SOCOMEC...
Page 77
Class 0.2 DIRIS Digiware I module alone Class 0.5 with TE, iTR or TF sensors Class 1 with TR sensors Connection Specific Socomec cable with RJ12 connectors Inputs - DIRIS Digiware I-4x Number of inputs Type / Power supply Non-insulated input, internal polarisation 12 VDC max., 1mA...
Removable screw terminal block, 2x2 positions, stranded or solid 0.14 - 1.5 mm² cable. Use Copper Conductors Only. 16.1.4. Communication characteristics Digiware BUS Function Connection between DIRIS Digiware modules Cable type Specific SOCOMEC cable with RJ45 connections RS485 Connection type 2 - 3 half duplex wires Protocol Modbus RTU Baudrate...
UL installation: The DIRIS Digiware system must be enclosed in an NRTL certified electrical/fire enclosure, listed Industrial Control Panel Equipment, or similar equipment. 16.1.8. Service life MTTF (mean time to failure) > 100 years DIRIS Digiware - 542875G - SOCOMEC...
Altitude < 2,000 m PEP ecopassport - ISO 14025 TE sensors: SOCO-2014-03-v1-fr, SOCO-2014-03-v1-en UL 61010 Connection SOCOMEC RJ12 cables: UTP, unshielded, twisted pair, straight, AWG24, 600V, CATV, -10 ... +70°C TE - solid-core sensor TE-90 Model TE-90 Nominal current range In (A) 600 - 2000 A Max.
Page 81
TR/iTR - Split-core sensor Model TR-10 / iTR-10 TR-14 / iTR-14 TR-21 / iTR-21 TR-32 / iTR-32 Nominal current range In (A) 26 - 63 40 - 160 63 - 250 160 - 600 Max. current (A) 75.6 Weight (g) Max.
Front panel protection index IP65 Weight D-30: 160 g 16.3.2. DIRIS D-30 communication characteristics Type of screen Local single-point screen for DIRIS Digiware I-4x Self-powered and data Upgrade and configuration via type B micro USB connector DIRIS Digiware - 542875G - SOCOMEC...
Orders 1 to 63 THD-Ri (relative to the fundamental, relative to the RMS value) Current harmonics 1 with sensors TE, TR/iTR or TF Centralised remote control signals *With SOCOMEC RJ12 and RJ45 connection cables. DIRIS Digiware - 542875G - SOCOMEC...
(relative to the fundamental, relative to the RMS value) Voltage harmonics THDi, Total harmonic distortion rate of the current Rank 1 to 63 THD-Ri (relative to the fundamental, relative to the RMS value) Current harmonics Centralised remote control signals DIRIS Digiware - 542875G - SOCOMEC...
Page 86