INSTALLATION AND OPERATING MANUAL
DIRIS Digiware AC
Multi-circuit Power Metering and Monitoring System
www.socomec.com/en/diris-digiware

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TR-10 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for socomec TR-10

  • Page 1 INSTALLATION AND OPERATING MANUAL DIRIS Digiware AC Multi-circuit Power Metering and Monitoring System www.socomec.com/en/diris-digiware...
  • Page 2: Table Of Contents

    ............... 39 DIRIS Digiware - 542875G - SOCOMEC...
  • Page 3 ................66 DIRIS Digiware - 542875G - SOCOMEC...
  • Page 4 ................85 DIRIS Digiware - 542875G - SOCOMEC...
  • Page 5 DIRIS Digiware - 542875G - SOCOMEC...
  • Page 6: Documentation

    All documentation relating to DIRIS Digiware and its associated sensors is available on the SOCOMEC website at the following address: www.socomec.com/en/diris-digiware Related instruction manuals Additional instruction manuals linked to the DIRIS Digiware system can be found on the Socomec website: Instruction manual Reference Easy Config System - Configuration Software...
  • Page 7: Hazards And Warnings

    • The auxiliary power supply voltage indicated on the device is observed: 24 VDC ± 10%. • The use of a SOCOMEC 230 VAC / 24 VDC power unit or a 24 VDC max 20 W class 2 power unit / SELV according to UL1310.
  • Page 8: Responsibility

    Before commissioning your DIRIS Digiware system, make sure all equipment operate under the latest firmware versions. The latest firmware versions are available on the Socomec website. The firmware upgrade is done using the Product Upgrade Tool software, by connecting a laptop to the Micro USB port of your DIRIS Digiware equipment.
  • Page 9: Introduction

    Thanks to its architecture, DIRIS Digiware can be easily integrated into an energy management system which requires a large number of loads to be monitored. * PMD: Power Metering and Monitoring Device in accordance with IEC 61557-12. DIRIS Digiware - 542875G - SOCOMEC...
  • Page 10: Range

    Ref. 4829 0129 Ref. 4829 0110 Ref. 4829 0112 DIRIS Digiware U-20 DIRIS Digiware I-45 DIRIS Digiware I-31 DIRIS Digiware I-61 Ref. 4829 0106 Ref. 4829 0131 Ref. 4829 0111 Ref. 4829 0113 DIRIS Digiware U-30 DIRIS Digiware I-33 Ref. 4829 0102 Ref. 4829 0128 DIRIS Digiware I-35 Ref. 4829 0130 DIRIS Digiware - 542875G - SOCOMEC...
  • Page 11 Ref. 4829 0160 DIRIS Digiware S-135 Ref. 4829 0161 DIRIS Digiware S-Datacenter Ref. 4829 0162 IO input/output modules DIRIS Digiware IO-10 DIRIS Digiware IO-20 Digital inputs/outputs Analogue inputs DIRIS Digiware IO-10 DIRIS Digiware IO-20 Ref. 4829 0140 Ref. 4829 0145 DIRIS Digiware - 542875G - SOCOMEC...
  • Page 12: Principle

    5.1.2. Principle DIRIS Digiware U DIRIS Digiware I Voltage measurement Current inputs (3I) Multipoint display DIRIS Digiware D Communication gateway DIRIS Digiware M DIRIS Digiware - 542875G - SOCOMEC...
  • Page 13 DIRIS Digiware S DIRIS Digiware I DIRIS Digiware I Current inputs (4I) DIRIS Current Digiware IO inputs (6I) Inputs/ outputs Current sensors TE, TR/iTR or TF DIRIS Digiware - 542875G - SOCOMEC...
  • Page 14: Functions

    DIRIS Digiware D-70 display - Time synchronisation done by the DIRIS Digiware M-50/M-70 gateway and DIRIS Digiware D-50/D-70 display - Auto-Discovery of slave modules from the DIRIS Digiware M gateway and DIRIS Digiware D display DIRIS Digiware - 542875G - SOCOMEC...
  • Page 15: Measured Electrical Parameters

    Voltage dips, swells and interruptions according to EN50160 • Alarms Thresholds • Data logging Trends of average values • Format Width/Number of modules 18 mm / 1 18 mm / 1 18 mm / 1 Part number 4829 0105 4829 0106 4829 0102 DIRIS Digiware - 542875G - SOCOMEC...
  • Page 16 10A / 63A 10A / 63A 1P+N 1P+N Load type accepted 2P+N 2P+N 1P+N 3P+N 3P+N Metering ± kWh, ± kvarh, kVAh • • • Multi-tariff (max 8) • Load curves / demand profiles • • DIRIS Digiware - 542875G - SOCOMEC...
  • Page 17 DIRIS Digiware IO IO-10 IO-20 Application Metering / Monitoring / Analysis Number of digital inputs/outputs Number of analogue inputs Format Width 18 mm 18 mm Number of modules Part number 4829 0140 4829 0145 DIRIS Digiware - 542875G - SOCOMEC...
  • Page 18: Dimensions

    0.24 1.97 2.56 5.1.5.2. D-50 & D-70 displays Dimensions in/mm 3.62 1.22 0.63 5.1.5.3. DIRIS Digiware C, U & I-3x, I-6x, IO-x 0.19 Dimensions in/mm C-3x U-xx I-6x I-3x IO-x 1.73 0.59 0.70 1.42 2.56 DIRIS Digiware - 542875G - SOCOMEC...
  • Page 19 5.1.5.4. DIRIS Digiware S-xx 2.13 Dimensions in/mm 0.45 0.61 0.61 1.10 15.5 15.5 11,5 0.31 5.1.5.5. DIRIS Digiware I-4x Dimensions in/mm 0.83 1.06 1.76 25.5 2.28 2.83 DIRIS Digiware - 542875G - SOCOMEC...
  • Page 20: Presentation Of The Associated Current Sensors

    TE / TR/iTR / TF TE / TR/iTR / TF For connecting the current sensors, use SOCOMEC cables or RJ12 straight cables, twisted pair, unshielded, 600 V -10°C / +70°C. It is recommended that all the current sensors be installed in the same direction.
  • Page 21: Te Solid-Core Current Sensors

    Maximum l Part number 4829 0500 4829 0501 4829 0502 4829 0503 4829 0504 4829 0505 TE-90 Pitch 90 mm Nominal current range In 600 - 2000 A Maximum l 2400 A Part number 4829 0506 DIRIS Digiware - 542875G - SOCOMEC...
  • Page 22 Aperture (W) Ø 8.4 13.5 x 13.5 21 x 21 31 x 31 41 x 41 0.69 0.69 0.77 0.85 17.5 17.5 19.5 21.5 TE-90 3.54 0.08 0.97 24.6 2.52 / 64 0.77 19.7 1.42 DIRIS Digiware - 542875G - SOCOMEC...
  • Page 23: Tr/Itr Split-Core Current Sensors

    TR-10 / i TR-10 TR-14 / i TR-14 TR-21 / iTR-21 TR-32 / iTR-32 1.74 2.63 2.56 3.38 1.02 1.14 1.45 2.08 1.10 1.10 1.69 1.85 0.55 0.82 1.26 0.59 0.90 1.30 0.39 0.55 0.82 1.26 Diameter DIRIS Digiware - 542875G - SOCOMEC...
  • Page 24: Tf Flexible Current Sensors

    1.57 3.15 4.72 7.87 11.81 23.62 Diameter D 4.96 9.88 14.84 24.72 37.09 74.21 Perimeter P 1885 8.04 x 0.75 x 0.6 Integrator 128 x 19 x 15 3.94 3.94 Ø 0.33 Ø 8.3 DIRIS Digiware - 542875G - SOCOMEC...
  • Page 25: Adaptor For 5A Current Transformers

    5A adaptor 5 A I nom. 6 A I max. 4829 0599 Part number 5.2.4.2. Dimensions Dimensions in/mm 5A adapter 1.10 x 0.79 x 1.77 LxHxD 28 x 20 x 45 Ø 0.33 Aperture (W) Ø 8.4 DIRIS Digiware - 542875G - SOCOMEC...
  • Page 26: Installation

    0.29 or 0.59 in 7.5 or 15 mm 6.2.2. DIRIS Digiware C, U, I-3x, I-6x, IO-x - backplate-mounting 0.19 in 5 mm Type of screw: M4 Tightening torque: 0.5 Nm Washer diameter 0.47 in / 12 mm max. DIRIS Digiware - 542875G - SOCOMEC...
  • Page 27: Diris Digiware I-4X - Din Rail Mounting

    Position I Position II 6.2.4. DIRIS Digiware I-4x - back-plate mounting Mounting of the brackets on the top and bottom Type of screw: M4 of the Tightening torque: 0.5 Nm module. Washer diameter 0.47 in / 12 mm max. DIRIS Digiware - 542875G - SOCOMEC...
  • Page 28: Diris Digiware S - Din Rail Mounting

    Step 1: Insert the tool through one of the current inputs and into the corresponding breaker terminal. Step 2: Tighten the associated screw(s). Please refer to the operating instructions of the protective device for additional information related to its installation. Ref: 4829 0196 (x10) DIRIS Digiware - 542875G - SOCOMEC...
  • Page 29: Accessories Overview

    The dimensions of the tightening clamp must not exceed 4 mm x 2 mm. 6.2.8. Accessories overview Part number Description 4829 0195 DIN-rail and back plate fixing tool (x10) 48290196 Temporary MCB insert (x10) DIRIS Digiware - 542875G - SOCOMEC...
  • Page 30: Installing Te Solid-Core Sensors

    4829 0501 4829 0502 TE-25 25 mm 4829 0503 TE-35 35 mm 4829 0504 TE-45 45 mm 4829 0505 TE-55 55 mm 4829 0506 TE-90 90 mm 6.3.2. DIN rail mounting TE-18 -> TE-55 DIRIS Digiware - 542875G - SOCOMEC...
  • Page 31 Note: it is possible to fix the TE-90 sensor to a DIN rail to make it easier to install. This is a temporary installation. Remove the clamps to install the TE-90 sensors on the DIN rail. DIRIS Digiware - 542875G - SOCOMEC...
  • Page 32: Back-Plate Mounting

    6.3.3. Back-plate mounting TE-18 1x diameter 0.17 / 4.2 M4 max 1 Nm 1.05 26.8 0.81 20.5 TE-25 - > TE-55 diameter 0.20 / 5.2 M5 max 1 Nm DIRIS Digiware - 542875G - SOCOMEC...
  • Page 33 TE-90 Removing the clamps Ø 0.20 Ø 5.2 Note: remove the clamps to install the TE-90 sensors on the back-plate. DIRIS Digiware - 542875G - SOCOMEC...
  • Page 34: Installing On A Cable With Clamping Collar

    Note: remove the clamps to install the TE-90 sensors on a cable with clamping collar. Do NOT clamp or pull out NON-INSULATED conductors carrying DANGEROUS VOLTAGE which could cause an electric shock, burn or arc flash. Ref. IEC 61010-2-032 DIRIS Digiware - 542875G - SOCOMEC...
  • Page 35: Bar Mounting

    The jaws must be perpendicular to the holding notches. Do NOT clamp or pull out NON-INSULATED conductors carrying DANGEROUS VOLTAGE which could cause an electric shock, burn or arc flash. Ref. IEC 61010-2-032 DIRIS Digiware - 542875G - SOCOMEC...
  • Page 36: Sensors Assembly

    Mounting accessories for sensor combination: Part number Linear assembly Staggered assembly 4829 0598 These accessories must be ordered separately. 6.3.7. Sealing accessories for sensors Sealing case for terminal Part number 4829 0600 These accessories must be ordered separately. DIRIS Digiware - 542875G - SOCOMEC...
  • Page 37: Installing Tr/Itr Split-Core Sensors

    Do NOT clamp or pull out NON-INSULATED conductors carrying DANGEROUS VOLTAGE which could cause an electric shock, burn or arc flash. Ref. IEC 61010-2-032. Before closing the TR /iTR sensor, check that the air gap is clean (no contamination or corrosion). DIRIS Digiware - 542875G - SOCOMEC...
  • Page 38: Installing Tf Flexible Current Sensors

    Centred position for the best measurement Do NOT clamp or pull out NON- INSULATED conductors carrying DANGEROUS VOLTAGE which could cause an electric shock, Centred position for the best burn or arc flash. measurement Ref. IEC 61010-2-032 DIRIS Digiware - 542875G - SOCOMEC...
  • Page 39: Installing The 5A Adapter

    6.6. Installing the 5A adapter 5A secondary current transformer Do NOT clamp or pull out NON-INSULATED conductors carrying DANGEROUS VOLTAGE which could cause an electric shock, burn or arc flash. Ref. IEC 61010-2-032. DIRIS Digiware - 542875G - SOCOMEC...
  • Page 40: Connection

    0.14 mm -> 1.5 mm flexible 7 mm Use Copper conductors only RS485 line polarisation Current sensors OFF = RS485 line polarisation TE, TR/iTR or TF disabled (by default) ON = RS485 line polarisation enabled DIRIS Digiware - 542875G - SOCOMEC...
  • Page 41 Only use a SOCOMEC Digiware bus cable (UTP RJ45 straight, twisted pair, unshielded, AWG24, 600V CAT V (-10 ... +70°C). When wiring, make sure you separate the low voltage (LV) section and the very low voltage (SELV) section to prevent any risk of electric shock.
  • Page 42 Protection 1A gG Protection 1A gG (*) The use of a 1A / 24 VDC fuse protection is recommended if the 24 VDC power supply is not provided by Socomec. For North America, the use of recognized fuses is mandatory.
  • Page 43: Connecting The Current Sensors

    TE / TR/iTR / TF TE / TR/iTR / TF TE / TR/iTR / TF - For connecting the current sensors, only use a SOCOMEC RJ12 cables (UTP unshielded, twisted pair, straight, AWG24, 600V, CATV, -10 ... +70°C). - Always connect input I01 first.
  • Page 44: Connecting To The Electrical Network And Loads

    1, 2, 3 or 4 sensors for balanced or unbalanced loads. The overall accuracy of the measurement chain (DIRIS Digiware + sensors) is guaranteed. To guarantee this accuracy, SOCOMEC current sensor connection cables or equivalent must be used. 7.3.1. Configurable loads based on the network type...
  • Page 45 Fuse: 0.5 A gG / BS 88 2A gG / 0.5 A class CC Listed fuses for UL application. V1 V2 V3 VN V1 V2 V3 VN V1 V2 V3 VN V1 V2 V3 VN V1 V2 V3 VN V1 V2 V3 VN V1 V2 V3 VN DIRIS Digiware - 542875G - SOCOMEC...
  • Page 46 V1 V2 V3 VN V1 V2 V3 VN V1 V2 Fuse: 0.5 A gG / BS 88 2A gG / 0.5 A class CC Listed fuses for UL application. V1 V2 V3 VN V1 V2 V3 VN DIRIS Digiware - 542875G - SOCOMEC...
  • Page 47 V1 V2 V3 VN V1 V2 V3 VN Three-phase 3P – 3CT + 3P – 1CT (x3) (1 three-phase load and 3 three-phase balanced load) V1 V2 V3 VN V1 V2 V3 VN V1 V2 V3 VN DIRIS Digiware - 542875G - SOCOMEC...
  • Page 48 Below are some connection examples of the DIRIS Digiware S module: 3P+N - 3CT 3P - 3CT V1 V2 V3 VN V1 V2 V3 VN V1 V2 V3 VN V1 V2 V3 VN V1 V2 V3 VN V1 V2 V3 VN DIRIS Digiware - 542875G - SOCOMEC...
  • Page 49: Connection Of The Functional Earth

    It is recommended that the functional earth be connected to guarantee optimum measurement accuracy and better emissivity/immunity for the electromagnetic compatibility (class B in conducted emission). In order to use the VirtualMonitor and AutoCorrect technologies, Earth must be connected to the DIRIS Digiware U module. DIRIS Digiware - 542875G - SOCOMEC...
  • Page 50: Digiware Bus

    50 m reel + 100 connectors 4829 0185 Use the shortest possible length of cable to optimise the electromagnetic emissions. The total maximum length must not exceed 100 metres. Use only SOCOMEC RJ45 cables for the Digiware bus. DIRIS Digiware - 542875G - SOCOMEC...
  • Page 51: Digiware Bus Termination

    DIRIS Digiware U-xx 0.72 Module current DIRIS Digiware I-3x 0.52 DIRIS Digiware I-4x 1.125 DIRIS Digiware I-6x DIRIS Digiware IO-10 DIRIS Digiware IO-20 DIRIS Digiware S-xx 0.35 Repeater DIRIS Digiware C-32 Single-point display DIRIS D-30 DIRIS Digiware - 542875G - SOCOMEC...
  • Page 52: Calculation Rules For The Max. Number Of Devices On The Digiware Bus

    Socomec has estimated (but this can vary from one connector to another) that the power loss of an RJ45 female/ female connector averages 0.1 W and represents an additional 3.33m of RJ45 cable length within the Digiware bus.
  • Page 53: Digiware Bus Repeater

    24 VDC 24 VDC I-4x I-4x power supply power supply The DIRIS Digiware U voltage module must be located upstream of the repeater. The repeater has a 24VDC power supply. DIRIS Digiware C-32 24VDC DIRIS Digiware - 542875G - SOCOMEC...
  • Page 54: Status And Leds

    (IN1, IN2, weight of input 1 (IN1) configured in IN3, IN4) configured in logical mode pulse meter mode (*) Network rotation alarm possibly indicating a configuration error DIRIS Digiware - 542875G - SOCOMEC...
  • Page 55: Diris Digiware S

    The voltage detection feature is an indication of the presence or the absence of voltage on one of the phases. It should only be used as an indication, and must not replace the use of a voltage tester. In addition, the nominal voltage must be correctly configured in the DIRIS Digiware U module DIRIS Digiware - 542875G - SOCOMEC...
  • Page 56: Auto-Discovery Process

    - FAST (default mode): this mode will only detect DIRIS Digiware modules on the Digiware bus and RS485 bus, DIRIS B and DIRIS A-40 on the RS485 bus. - FULL: this mode will also detect other Socomec PMDs (DIRIS A) and meters (COUNTIS E) connected on the RS485 bus.
  • Page 57 If you would like to assign specific Modbus addresses to the devices connected to the M-50/M-70 gateway, launch the auto-discovery from the Easy Config System software, and change the Modbus addresses of slave devices directly from the dashboard of the M-50/M-70 gateway (see 13.2). DIRIS Digiware - 542875G - SOCOMEC...
  • Page 58: Auto-Discovery From The Diris Digiware D Display

    6. The auto-discovery process is finished, the D-xx display shows the number of discovered devices (3 in our example). The COM LEDs blink when communication is on-going between the D-xx display and downstream modules. DIRIS Digiware - 542875G - SOCOMEC...
  • Page 59: Communication

    - A 120 Ω resistor must be added at the start of the RS485 link - A 120 Ω resistor must be added at the end of the RS485 link - A terminating resistor must be added at the end of the Digiware bus. DIRIS Digiware - 542875G - SOCOMEC...
  • Page 60: Ethernet Communication

    - An end of line resistor must be added at the end of the Digiware bus. 11.5. Communication tables The communication tables and associated explanations can be found on the documentations page for DIRIS Digiware on the SOCOMEC website: www.socomec.com/operating-instructions_en.html DIRIS Digiware - 542875G - SOCOMEC...
  • Page 61: Configuration

    Config System must be installed before using the USB connection. Before configuring the DIRIS Digiware system, please make sure it operates using the latest available firmware versions. The latest firmware versions are available on the Socomec website. 12.1. Connection modes >...
  • Page 62: Configuration Via Easy Config System

    The main settings of the DIRIS Digiware system (U, S, I, IO) can be configured from the DIRIS Digiware D-xx display directly. Refer to the manual for the DIRIS Digiware D display for more details. DIRIS Digiware - 542875G - SOCOMEC...
  • Page 63: Alarms

    - Via a digital input (for devices with digital inputs, such as DIRIS Digiware IO-10 and I-4x modules) Output report System alarms can be linked to a digital output for alarm reporting purposes. Delay A time delay can be configured at the start and the end of the alarm. DIRIS Digiware - 542875G - SOCOMEC...
  • Page 64: Measurement Alarms

    - Via a digital input (for devices with digital inputs, such as DIRIS Digiware IO-10 and I-4x modules) Output report Protection alarms can be linked to a digital output for alarm reporting purposes. Delay A time delay can be configured at the start and the end of the alarm. DIRIS Digiware - 542875G - SOCOMEC...
  • Page 65: Protection Counter Alarms

    - Via a digital input (for devices with digital inputs, such as IO-10, I-4x etc.) Output report Logical alarms can be linked to a digital output for alarm reporting purposes. Delay A time delay can be configured at the start and the end of the alarm. DIRIS Digiware - 542875G - SOCOMEC...
  • Page 66: Combination Alarms

    - Via a digital input (for devices with digital inputs, such as DIRIS Digiware I-4x) Output report The overcurrent alarm can be linked to a digital output for alarm reporting purposes. Delay A time delay can be configured at the start and the end of the alarm. DIRIS Digiware - 542875G - SOCOMEC...
  • Page 67: Virtualmonitor Technology: Monitoring Of Protective Devices

    Visualisation is available from the DIRIS Digiware D-50/D-70 displays and WEBVIEW, embedded in the DIRIS Digiware M-70/D-70 and DATALOG H80/H81. You must configure the type of protective device from the Easy Config System software in the “Protection” menu for the VirtualMonitor function to be used: DIRIS Digiware - 542875G - SOCOMEC...
  • Page 68 An example corresponding to the above illustration is given in the table below: Voltage measured on U module ? Yes, 230V L-N Voltage detected on S modules ? No, 0V Position of protective device Closed Open Closed DIRIS Digiware - 542875G - SOCOMEC...
  • Page 69 For the voltage detection (hence the VirtualMonitor technology) to work properly when using iTR current sensors, make sure the section of live conductors are above the minimal sections given in the table below: iTR Type iTR-10 iTR-14 iTR-21 iTR-32 Min cable section (mm²) DIRIS Digiware - 542875G - SOCOMEC...
  • Page 70: Autocorrect Technology: Automatic Detection Of Wiring Errors And Software Correction

    Ex.1: DIRIS Digiware I module and iTR current sensors, with phase inversion of current sensors 1 and 3. Let’s consider a phase inversion between current sensors 1 and 3, as showed in the following picture: DIRIS Digiware - 542875G - SOCOMEC...
  • Page 71  POSITIVE  • Now the wiring has been corrected in the software and power values are correctly calculated: >> AUTOCORRECT PC 1-2-3 INPUT  +/DIRECT  +/DIRECT  +/DIRECT PRESS OK TO LAUNCH AUTOCORRECT DIRIS Digiware - 542875G - SOCOMEC...
  • Page 72 • Press “OK” to launch AUTOCORRECT, and choose a positive power sign. The error mark is cleared and the cell WAY is no longer gray: >> AUTOCORRECT PC 1-2-3 INPUT  -/INV  +/DIRECT  +/DIRECT PRESS OK TO LAUNCH AUTOCORRECT DIRIS Digiware - 542875G - SOCOMEC...
  • Page 73: Identifying The Wiring Error From The Easy Config System Software

    If inconsistencies are detected, cells will be highlighted in red and an automatic software correction is possible by clicking on "AutoCorrect". DIRIS Digiware - 542875G - SOCOMEC...
  • Page 74 After clicking on "AutoCorrect" the association errors are corrected and there are no more red cells in the diagnostic table: You can also correct the wrong voltage/current association manually in the "Current Sensors" menu: DIRIS Digiware - 542875G - SOCOMEC...
  • Page 75 For the voltage detection (hence the AutoCorrect technology) to work properly, make sure the section of live conductors are above the minimal sections given in the table below: iTR Type iTR-10 iTR-14 iTR-21 iTR-32 Min cable section (mm²) DIRIS Digiware - 542875G - SOCOMEC...
  • Page 76: Technical Characteristics

    Network type Single-phase/ Two-phase / Two-phase with neutral / Three-phase / Three-phase with neutral Measurement by voltage transformer Primary: 400,000 VAC Secondary: 60, 100, 110, 173, 190 VAC Input consumption ≤ 0.1 VA Permanent overload 300 VAC Ph/N DIRIS Digiware - 542875G - SOCOMEC...
  • Page 77 Class 0.2 DIRIS Digiware I module alone Class 0.5 with TE, iTR or TF sensors Class 1 with TR sensors Connection Specific Socomec cable with RJ12 connectors Inputs - DIRIS Digiware I-4x Number of inputs Type / Power supply Non-insulated input, internal polarisation 12 VDC max., 1mA...
  • Page 78: Communication Characteristics

    Removable screw terminal block, 2x2 positions, stranded or solid 0.14 - 1.5 mm² cable. Use Copper Conductors Only. 16.1.4. Communication characteristics Digiware BUS Function Connection between DIRIS Digiware modules Cable type Specific SOCOMEC cable with RJ45 connections RS485 Connection type 2 - 3 half duplex wires Protocol Modbus RTU Baudrate...
  • Page 79: Environmental Characteristics

    UL installation: The DIRIS Digiware system must be enclosed in an NRTL certified electrical/fire enclosure, listed Industrial Control Panel Equipment, or similar equipment. 16.1.8. Service life MTTF (mean time to failure) > 100 years DIRIS Digiware - 542875G - SOCOMEC...
  • Page 80: Te, Tr/Itr And Tf Sensor Technical Characteristics

    Altitude < 2,000 m PEP ecopassport - ISO 14025 TE sensors: SOCO-2014-03-v1-fr, SOCO-2014-03-v1-en UL 61010 Connection SOCOMEC RJ12 cables: UTP, unshielded, twisted pair, straight, AWG24, 600V, CATV, -10 ... +70°C TE - solid-core sensor TE-90 Model TE-90 Nominal current range In (A) 600 - 2000 A Max.
  • Page 81 TR/iTR - Split-core sensor Model TR-10 / iTR-10 TR-14 / iTR-14 TR-21 / iTR-21 TR-32 / iTR-32 Nominal current range In (A) 26 - 63 40 - 160 63 - 250 160 - 600 Max. current (A) 75.6 Weight (g) Max.
  • Page 82: Electromagnetic Compatibility And Insulation Levels

    Front panel protection index IP65 Weight D-30: 160 g 16.3.2. DIRIS D-30 communication characteristics Type of screen Local single-point screen for DIRIS Digiware I-4x Self-powered and data Upgrade and configuration via type B micro USB connector DIRIS Digiware - 542875G - SOCOMEC...
  • Page 83: Diris Digiware D-50/D-70 & M-50/M-70 Characteristics

    -10 ... +55°C (IEC 60068-2-1 / IEC 60068-2-2) Storage temperature -40 ... +70°C (IEC 60068-2-1 / IEC 60068-2-2) Humidity +23°C/97% RH & +55°C/93% RH (IEC 60068-2-30) Installation category, Degree of pollution Device powered by SELV, 2 DIRIS Digiware - 542875G - SOCOMEC...
  • Page 84: Performance Classes

    Orders 1 to 63 THD-Ri (relative to the fundamental, relative to the RMS value) Current harmonics 1 with sensors TE, TR/iTR or TF Centralised remote control signals *With SOCOMEC RJ12 and RJ45 connection cables. DIRIS Digiware - 542875G - SOCOMEC...
  • Page 85: Diris Digiware S

    (relative to the fundamental, relative to the RMS value) Voltage harmonics THDi, Total harmonic distortion rate of the current Rank 1 to 63 THD-Ri (relative to the fundamental, relative to the RMS value) Current harmonics Centralised remote control signals DIRIS Digiware - 542875G - SOCOMEC...
  • Page 86 CORPORATE HQ CONTACT: SOCOMEC SAS 1-4 RUE DE WESTHOUSE 67235 BENFELD, FRANCE www.socomec.com 542875G...