Wayne HS Manual page 18

Oil burner
Hide thumbs Also See for HS:
Table of Contents

Advertisement

SPECIFICATIONS
Timing:
Safe Start Check: 5 seconds (approximately)
Lockout: 15, 30 or 45 seconds (factory-programmed)
Wayne Lockout Timing: 15 seconds
Recycle: 60 seconds (fixed)
Ignition Carryover: 10 seconds (fixed)
Electrical Ratings:
Inputs:
Voltage: 102 to 132 Vac, 120 Vac nominal
Current: 100 mA plus burner motor loads
Frequency: 60 Hz.
Outputs:
Burner Relay Contacts: 120 Vac, 10 full load
amperes (FLA), 60 locked rotor amperes
(LRA)
Thermostat Current Available: 100 mA
EnviraCOM™ Current Available: 150 mA
ignitor draws 3A (120 Vac, 360 VA), reduce the burner
motor FLA to 7A.
Typical Component Wire Color Code:
White: Neutral
Black: Line
Orange: Blower/Pump
Reduce burner FLA rating by
ignitor load. For example, if the
Figure 23: Oil Primary Wiring
Environmental Ratings:
Operating Ambient Temperature: -40°F to +150°F (-40°C to
+66°C)
Shipping Temperature: -20°F to +150°F (-29°C to +66°C)
Humidity: 90% relative humidity at 95°F (35°C), non-
condensing
Approvals:
Underwriters Laboratories Inc.: Recognized (File MP268).
Canadian Underwriters Laboratories Inc.
15