Manual of Electrical Installation for Pressure Probes KH-SIL2 series Code 85198C Edition 08-2022 Contents 1. General precautions pag 2 2. Transmitters with amplified analog output pag 2 pag 2 Standard installation pag 3 Electrical connections 3. Protection for outdoor installations of analog sensors pag 4 4.
1. General Precautions The system must be used only in accordance with the required protection level. The sensor must be protected against accidental knocks and used in accordance with the instrument’s ambient characteristics and per- formance levels. Sensors must be powered with non distributed networks. For outdoor installations or with cables longer than 30 m*, proceed as indicated at paragraph 3.
Electrical connections RATIOMETRIC AND VOLTAGE AMPLIFIED OUTPUT POWER SUPPLY Black White OUTPUT CURRENT AMPLIFIED OUTPUT – mod. E POWER SUPPLY SIGNAL Black Interfaces with SRP/CS and voltage devices The interface with SRP/CS (Safety Related Part of a Control System) is made by mean of multipolar connectors showed on pictures below, where the connections are specified in case of amplified voltage output (3 wire) or current output (2 wire system, the sensor is connected in series with the current loop).
3. Protection for outdoor installations of analog sensors Pressure / Analog current output CAL signals if any do not require protection PLC side Transducer side +24Vdc +24Vdc B72210-S-250-K01 B72210-S-250-K01 machine ground PLC ground PLC side Transducer side +OUT B72210-S-250-K01 PLC side Ground Pressure / Analog voltage output CAL signals if any do not require protection...
4. Technical specifications Output signal VOLTAGE RATIOMETRIC CURRENT Accuracy at room temperature (1) < ± 0.5% FS Pressure ranges (2) From 4 bar to 1000 bar (See table) Overvoltage 32 Vdc max Overpressure (without degrading performance) See table Pressure containment (burst test) See table Pressure Media Fluids compatible with Stainless Steel AISI 430F and 17-4 PH...
5. Functional Safety (content according to IEC/EN 62061 paragraph 7) 5.1 Application The pressure sensor KH performs the following safety function: correct reading and transduction of pressure to individuate overpressure. Reading and transduction is considered cor- rect when it is within the specifications declared in the datasheet and in the Operating Manual. The SIL parameters of the transducer are shown in the table below: Parameter Value...
5.2 Restrictions of use The device must only be used in accordance with these operating instructions for mechanical installation, electrical con- nection, environmental conditions and use in order to maintain the declared SIL. The sensors must be powered by non-distributed networks and in any case with a length of less than 30 m.
5. If the problem persists, you should send back the probe to Factory for repair. via Sebina, 74 - 25050 PROVAGLIO D’ISEO (BS) - ITALIA tel. 0309888.1 - fax. 0309839063 - Internet: http://www.gefran.com 85198C_Manual of Electrical Installation for Pressure Probes KH-SIL2-Mobyle-series_08-2028_ENG...