Vertical Vent Tables And Figures - Superior SDV35-2 Installation Instructions Manual

Direct-vent gas fireplaces
Hide thumbs Also See for SDV35-2:
Table of Contents

Advertisement

SUPERIOR
VERTICAL VENT FIGURES/TABLES
Note: Secure Vent
(rigid vent pipe) is
®
shown in the figures; Secure Flex
vent pipe) may also be used.
Note: It is very important that the horizontal/
inclined run be maintained in a straight
(no dips), slightly elevated plane. The
recommended incline is approximately 1/4 in.
per foot (20 mm per meter) horizontal, in a
direction away from the fireplace. The rise per
foot run ratios that are smaller are acceptable
all the way down to at or near level.
Note: SV4.5VF (Secure Vent), SF4.5VF
(Secure Flex
) firestop/spacer must be
®
used anytime vent pipe passes through
a combustible floor or ceiling. SV4.5HF
(Secure Vent), SF4.5HF (Secure Flex
firestop/spacer must be used anytime vent
pipe passes through a combustible wall.
Note: Two 45 degree elbows may be used in
place of one 90 degree elbow. The same rise
to run ratios, as shown in the venting figures
for 90 elbows, must be followed if 45 degree
f i r e - p a r t s . c o m
elbows are used.
Note: An elbow is acceptable as 1 foot of
vertical rise, except where an elbow is the
only vertical component in the system. (See
Figure 38 on Page 21).
Max. 40 ft
Ceiling
(12.2 m)
Firestop/
Spacer
SV4.5VF*
*When using
Secure Flex, use
Ceiling Firestop/
Spacer SF4.5VF.
A Vent Restrictor, as shown in
Figure 17 on Page 13, must be used in
this application.
Figure 29: Top Vent—STRAIGHT
• DIRECT-VENT GAS FIREPLACES (SDV35-N-2) • INSTALLATION INSTRUCTIONS
®
H Maximum
(flexible
®
feet
(meters)
2
(0.610)
4
(1.219)
6
(1.829)
8
(2.438)
V + H = 40 feet (12.2 meters) Max.
H = 8 feet (2.4 meters) Max.
Ratio V to H ratio is 1:2
This table shows a 1 (V) to 2 (H) ratio.
For every 1 foot of (V) vertical, you are
allowed 2 feet of (H) horizontal run, up
to a maximum horizontal run of 8 feet.
)
®
Example: If 8 feet of (H) horizontal
vent run is needed, then 4 feet
minimum (V) vertical vent will
be required.
Figure 30: Rear Vent—ONE 90-DEGREE ELBOW
V1
*When using Secure Flex, use
Ceiling Firestop/Spacer SF4.5VF.
**When using Secure Flex, use
Wall Firestop/Spacer SF4.5HF.
Figure 31: Top Vent—TWO 90-DEGREE ELBOWS
Under no circumstances, may separate sections of concentric flexible vent
pipe be joined together.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
TABLE A
V Minimum
(meters)
feet
1
(0.305)
2
(0.610)
3
(0.914)
V
4
(1.219)
H
Ceiling
Firestop/Spacer
SV4.5VF*
Wall
Firestop/Spacer
SV4.5HF**
WARNING
Ceiling
Firestop/Spacer
SV4.5VF*
*When using Secure Flex, use
Ceiling Firestop/Spacer SF4.5VF.
H
Note: Install the U-shaped vent restrictor in
any vent run with more than 8 ft of vertical
rise (See Page 13).
TABLE B
H Maximum
V Minimum
(meters)
feet
feet
(1.524)
5
Elbow Only
(1.524)
5
1
(3.048)
10
2
15
(4.572)
3
(6.096)
20
4
V + V
+ H = 40 feet (12.2 m) Max.
1
H = 20 feet (6.096 meters) Max.
Example: If 20 feet of (H) horizontal vent
run is needed, then 4 feet minimum of
(V) vertical vent will be required.
This table shows a 1 (V) to 5 (H) ratio.
For every 1 foot of (V) vertical, you are
V
allowed 5 feet of (H) horizontal run, up to
a maximum horizontal run of 20 feet.
An elbow is acceptable as 1 foot of
vertical rise except where an elbow is the
only vertical component in the system.
See Figure 38.
Note: Install the U-shaped vent restrictor
in any vent run with more than 8 ft of
vertical rise (See Page 13).
(meters)
(0.305)
(0.610)
(0.914)
(1.219)
17

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sdv35-n-2

Table of Contents