5. Thermistor resistance values
5-1. Indoor unit
¢ Room temperature thermistor
Temperature °F (°C)
14.0 (-10.0)
23.0 (-5.0)
32.0 (0.0)
41.0 (5.0)
50.0 (10.0)
59.0 (15.0)
68.0 (20.0)
77.0 (25.0)
86.0 (30.0)
95.0 (35.0)
104.0 (40.0)
113.0 (45.0)
¢ Heat exchanger temperature thermistor
Temperature °F (°C)
-22.0 (-30.0)
-13.0 (-25.0)
-4.0 (-20.0)
5.0 (-15.0)
14.0 (-10.0)
23.0 (-5.0)
32.0 (0.0)
41.0 (5.0)
50.0 (10.0)
59.0 (15.0)
68.0 (20.0)
77.0 (25.0)
86.0 (30.0)
95.0 (35.0)
104.0 (40.0)
113.0 (45.0)
122.0 (50.0)
131.0 (55.0)
140.0 (60.0)
149.0 (65.0)
5-1. Indoor unit
Resistance (kΩ)
58.25
44.03
33.62
25.93
20.18
15.84
12.54
10.00
8.04
6.51
5.30
4.35
Resistance (kΩ)
1,131.91
804.52
579.59
422.89
312.27
233.21
176.03
134.23
103.34
80.28
62.91
49.70
39.57
31.74
25.64
20.85
17.06
14.05
11.64
9.69
- (03-42) -
Voltage (V)
0.73
0.93
1.15
1.39
1.66
1.94
2.22
2.50
2.77
3.03
3.27
3.49
Voltage (V)
0.21
0.29
0.40
0.53
0.69
0.88
1.10
1.36
1.63
1.92
2.21
2.51
2.79
3.06
3.30
3.53
3.73
3.90
4.02
4.19