Fujitsu ASUH09LPAS Service Manual page 48

Wall mounted type
Hide thumbs Also See for ASUH09LPAS:
Table of Contents

Advertisement

Check point 4. Check serial signal (reverse transfer signal)
Check serial signal (Forward transfer signal)
Check if indicated value swings between AC 30 V and AC 130 V at outdoor unit terminal 2—3.
If it is abnormal, replace main PCB.
If it is abnormal, check indoor unit fan motor. (Indoor unit fan motor in
tion"
on page 03-36)
If indoor unit fan motor is abnormal, replace indoor unit fan motor and main PCB.
Check point 1-2. Check external cause such as noise
Check the complete insulation of the grounding.
Check if there is any equipment that causes harmonic wave near the power cable (Neon light
bulb or any electronic equipment which causes harmonic wave).
2-2. E: 11. Serial communication error (Serial forward transfer error) (Indoor unit)
BLACK
1
WHITE
2
RED
3
BLACK
L1
WHITE
L2
End
End
+
-
- (03-6) -
"Service parts informa-
2. Troubleshooting with error code