Compressor Frequency Limitation By Outdoor Temperature - Fujitsu ASUG12LZAS Service Manual

Wall mounted type
Hide thumbs Also See for ASUG12LZAS:
Table of Contents

Advertisement

1-5. Compressor frequency limitation by outdoor temperature

The minimum compressor frequency is limited by outdoor temperature as below.
• Cooling/Dry mode
Model name
AOUG09LZAS1
AOUG12LZAS1
AOUG15LZAS1
1-5. Compressor frequency limitation by outdoor temperature
F zone
100.4°F
(38°C)
E zone
66.2°F
(19°C)
D zone
50.0°F
(10°C)
C zone
32.0°F
(0°C)
B zone
14.0°F
(-10°C)
A zone
Outdoor temperature zone
A zone
B zone
C zone
D zone
E zone
F zone
A zone
B zone
C zone
D zone
E zone
F zone
- (04-5) -
Limitation of compressor
frequency
37 rps
37 rps
37 rps
28 rps
1 rps
22 rps
33 rps
33 rps
33 rps
25 rps
10 rps
20 rps
1. Compressor frequency control

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents