E: 11. Serial Communication Error (Serial Forward Transfer Error) (Indoor Unit) - Fujitsu ASUG12LZAS Service Manual

Wall mounted type
Hide thumbs Also See for ASUG12LZAS:
Table of Contents

Advertisement

2-2. E: 11. Serial communication error (Serial forward transfer
error) (Indoor unit)
Indicator
Indoor unit
Detective actuator
Indoor unit
Forecast of cause
Check point 1. Reset the power and operate
Does error indication show again?
→ If no, go to
"Check point
Check point 2. Check connection
Check any loose or removed connection line of indoor unit and outdoor unit.
Check connection condition is control unit. (If there is loose connector, open cable or mis-wiring.)
→ If there is an abnormal condition, correct it by referring to the installation manual or the DESIGN
& TECHNICAL MANUAL.
Check point 3. Check the voltage of power supply
Check the voltage of power supply
Check if AC 187 V (AC 208 V -10%) to AC 253 V (AC 230 V +10%) appears at
outdoor unit terminal L—N.

2-2. E: 11. Serial communication error (Serial forward transfer error) (Indoor unit)

Operation indicator
Timer indicator
Economy indicator
Error code
Main PCB
When the indoor unit cannot receive the serial signal
from outdoor unit more than 2 minutes after power on,
or the indoor unit cannot receive the serial signal more
Fan motor
than 15 seconds during normal operation.
1-2".
- (03-12) -
1 time flash
1 time flash
Continuous flash
E: 11
Connection failure
External cause
Main PCB failure
Indoor unit fan motor failure
2. Troubleshooting with error code
+
-