1-5. Compressor frequency limitation by outdoor temperature

The minimum compressor frequency is limited by outdoor temperature as below.
• Cooling/Dry mode
Model name
AOYG18KATA
AOYG22KATA
1-5. Compressor frequency limitation by outdoor temperature
F zone
38°C
E zone
19°C
D zone
10°C
C zone
0°C
B zone
-10°C
A zone
Outdoor temperature zone
A zone
B zone
C zone
D zone
E zone
F zone
A zone
B zone
C zone
D zone
E zone
F zone
- (04-5) -
Limitation of compressor
frequency
36 rps
36 rps
28 rps
1 rps
1 rps
20 rps
30 rps
30 rps
22 rps
16 rps
13 rps
25 rps
1. Compressor frequency control