Page 1
Revision: WS-IOM (12-22) 1042506-0 Supersedes: — (Original Version) HYDRONIC UNIT HEATER INSTALLATION, OPERATION, AND MAINTENANCE MODEL WS ⚠ WARNING ⚠ • Be sure to read and understand the installation, operation, and service instructions in this manual. • Installation should be done by a qualified agency in accordance with these instructions. The qualified service agency installing this heater is responsible for the installation.
These unit heaters are listed by Intertek for use in the United States and in Canada . Installation Codes These units must be installed in accordance with local building codes . Local authorities having jurisdiction should be consulted before installation is made to verify local codes and installation procedure requirements . WS-IOM (12-22) 1042506-0...
Refer to sound level data listed in Table 2 when determining unit location based on acoustical considerations . Table 2. Acoustical Data Unit Size 18/24 23/33 44/62 60/85 78/110 96/120 140/175 190/238 300/350 Speed Sound level (dBa) @ 16-1/2 feet High WS-IOM (12-22) 1042506-0...
1 . Position vertical louver assembly (see Figure 3) on face of heater and align existing mounting holes . 2 . Secure vertical louver assembly to heater using fasteners provided in option kit . Figure 3. Vertical Louver Assembly WS-IOM (12-22) 1042506-0...
1 . Determine installation height and secure field-supplied brackets to wall as shown in using field-supplied hardware . Figure 5 2 . Raise heater using suitable hoist or lift and secure heater to brackets as shown in using M8 metric screws and flat washers provided . WS-IOM (12-22) 1042506-0...
8) sealed with pipe sealant . • Connect hot water piping in accordance with piping diagram shown in Figure • Connect steam piping in accordance with piping diagram shown in Figure 10 . Figure 8. Three-Part Joint Union and Ball Valve WS-IOM (12-22) 1042506-0...
Page 11
Figure 9. Hot Water Piping Diagram STEAM SLOPE SUPPLY STEAM SLOPE CONDENSATE CONDENSATE RETURN SUPPLY FLOW TRAP RETURN DRIP LEG AND FLOW TRAP DRIP LEG CLEANOUT DRAIN CLEANOUT DRAIN HORIZONTAL DISCHARGE VERTICAL DISCHARGE Figure 10. Steam Piping Diagram WS-IOM (12-22) 1042506-0...
NOTE: Internal motor wiring (for reference only): black wire from motor winding connects to U1, red wire from motor winding connects to V1, and green wire from motor winding connects to W1. CAPACITOR MOTOR FIELD- SUPPLIED OVER- MANUAL STARTER LOAD THERMOSTAT HIGH SPEED LOW SPEED Figure 11. Wiring Diagram WS-IOM (12-22) 1042506-0...
1 . Set thermostat at lowest setting . 2 . Turn ON electric power to heater . 3 . Open hot water or steam supply valve . 4 . Set thermostat to desired setting . Refer to Table 9 for operational sequence . WS-IOM (12-22) 1042506-0...
(2973) (3738) (6457) Air volume Hot water (cfm (m /hr) or steam 1250 1650 1550 2300 2850 4750 High (680) (850) (1461) (2124) (2804) (2634) (3908) (4842) (8071) Hot water Maximum High heating capacity (MBH) Steam High WS-IOM (12-22) 1042506-0...
The unit is designed to operate with a minimum of maintenance . However, to ensure long life and satisfactory performance, routine service is recommended . When servicing, follow standard safety procedures and those specific instructions and warnings in this manual . WS-IOM (12-22) 1042506-0...
. • Closed motors have self-lubricating bearings and are maintenance-free . If the motor is replaced, don’t forget to check fan rotation . WS-IOM (12-22) 1042506-0...
Need help?
Do you have a question about the WS and is the answer not in the manual?
Questions and answers