TSI Instruments 8630-PM-CRM Manual Supplement

TSI Instruments 8630-PM-CRM Manual Supplement

Premium clean room monitor

Advertisement

Quick Links

Model Number:
Product/System Title
Contents of this manual supplement include:
1) Sequence of operation
2) Menu structure drawing
3) Description of new software items
4) Deleted software menu item
5) Wiring diagram
6) Access Code
Manual Supplement
8630-PM-CRM
Premium Clean Room Monitor
:
Project:
Date:
Page 1 of 1
Released 4/9/04

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 8630-PM-CRM and is the answer not in the manual?

Questions and answers

Summary of Contents for TSI Instruments 8630-PM-CRM

  • Page 1 Manual Supplement Model Number: 8630-PM-CRM Product/System Title Premium Clean Room Monitor Contents of this manual supplement include: 1) Sequence of operation 2) Menu structure drawing 3) Description of new software items 4) Deleted software menu item 5) Wiring diagram 6) Access Code...
  • Page 2: Sequence Of Operation

    Sequence of Operation The Model 8630-PM-CRM monitors room pressure by utilizing a through-the-wall pressure sensor. The Model 8630-PM-CRM features high and low pressure alarms for up to two independent sensors. A minimum supply volume alarm is also present. Additinally, the Model 8630-PM-CRM supports digital communications over an RS-485 network and an analog pressure output.
  • Page 3 Manual Supplement Description of New Software Items The Model 8630-PM-CRM has additional software items. Alarm Menu Menu Item Description LOW ALARM The LOW ALARM and SEC LOW ALARM items set the SEC LOW ALM low pressure alarm set points for the primary and secondary pressure sensor.
  • Page 4 PRESS AOUT The PRESS AOUT item is used to vary the analog output from the Model 8630-PM-CRM. When this item is entered, a number will be shown on the display indicating the last analog output value. The value displayed ranges from 0 to 255. The value 255 corresponds to the lowest voltage (current) output and 0 corresponds to the highest voltage (current) output.
  • Page 5: Sensor Type

    Manual Supplement SUP ALM REL The SUP ALM REL item is used to change the state of the minimum supply alarm relay. When this item is entered, the display will indicate either OPEN or CLOSED. The keys are used to toggle the state of the relay. The key is used to OPEN the alarm contact.
  • Page 6 Manual Supplement Flow Menu Menu Item Description SUP1 AREA The SUP1 AREA and SUP2 AREA items are used to input the duct sizes for the first and second supply. The duct sizes SUP2 AREA are needed to compute the air flowing into the room. These items require a flow sensor to be mounted in the proper supply duct.
  • Page 7: Configure Menu

    Manual Supplement Deleted Software Menu Items The following items have been replaced on the 8630-PM-CRM.: ALARM MENU NEG LOW ALARM NEG HIGH ALARM POS LOW ALARM POS HIGH ALARM MIN CFM ALM 2 LOW ALM 2 HIGH ALM CONFIGURE MENU...
  • Page 8: Wiring Diagrams

    Manual Supplement Wiring Diagrams MODEL 8630-CRM WIRING DIAGRAM – TSI SENSOR Project: Date: Page 8 of 8 Released 4/9/04...
  • Page 9 Manual Supplement MODEL 8630 - CRM MONITOR MODEL 8630-CRM MONITOR WIRING DIAGRAM - PRESSURE XDCR WIRING DIAGRAM - XDCR Project: Date: Page 9 of 9 Released 4/9/04...
  • Page 10: Access Codes

    Manual Supplement Access Codes The 8630-PM-CRM has a single access code for all menus. Each menu has the access code enabled individually; implementing the access code in one menu does not enable the access code in other menus. When an access code is required, pressing the following key sequence will provide access:...