Checking The Position Of The Speed Sensor - Riello RLS 130/EV Installation, Use And Maintenance Instructions

Dual fuel light oil/gas burner progressive two stage or modulating operation
Table of Contents

Advertisement

LIGHT OIL OPERATION
Pump
Delivery pressure must correspond with the Fig. 17.
The depression must be less than 0.45 bar
Unusual noise must not be evident during pump operation
If the pressure is found to be unstable or if the pump runs noisily,
the flexible hose must be detached from the line filter and the fuel
must be sucked from a tank located near the burner. This measure
permits the cause of the anomaly to be traced to either the suction
line or the pump.
If the problem lies in the suction line, check to make sure that the
filter is clean and that air is not entering the piping.
Filters
Check the filtering baskets on line and at nozzle present in the sys-
tem. Clean or replace if necessary.
If rust or other impurities are observed inside the pump, use a sep-
arate pump to lift any water and other impurities that may have de-
posited on the bottom of the tank.
Nozzles
It is advisable to replace nozzles every year during regular main-
tenance operations.
Do not clean the nozzle openings; do not even open them.
Flexible hoses
Check to make sure that the flexible hoses are still in good condi-
tion.
6.3

Checking the position of the speed sensor

The measurement of speed sensor 1)(Fig. 53) must
be respected!
WARNING
To calibrate the speed sensor, proceed as follows:
 loosen the screws 3) rest the sensor on the disc extension 2).
 Take the scale 4) as a reference, pull back the speed sensor
by about a notch so that the distance from the disc extension
2) is about 2 mm = 5/64 inch.
Key (Fig. 53)
1
Speed sensor
2
Disc
3
Screw
4
Scale
Maintenance
Fuel tank
Approximately every 5 years, or whenever necessary, suck any
water or other impurities present on the bottom of the tank using a
separate pump.
.
Combustion
.
In case the combustion values found at the beginning of the inter-
vention do not respect the standards in force or, in any case, do not
correspond to a proper combustion, contact the Technical Assis-
tant and have him carry out the necessary adjustments.
Gas leaks
Make sure that there are no gas leaks on the pipework between the
gas meter and the burner.
Gas filter
Change the gas filter when it is dirty.
Combustion
In case the combustion values found at the beginning of the inter-
vention do not respect the standards in force or, in any case, do not
correspond to a proper combustion, contact the Technical Assis-
tant and have him carry out the necessary adjustments.
39
GB
GAS OPERATION
4
3
20082216
3
1
2
Fig. 53
20096088

Advertisement

Table of Contents
loading

This manual is also suitable for:

20110941

Table of Contents