Inverter Connection - Riello RLS 130/EV Installation, Use And Maintenance Instructions

Dual fuel light oil/gas burner progressive two stage or modulating operation
Table of Contents

Advertisement

4.14.3 Inverter connection

Following, it is reported an example how to con-
nect the Inverter.
For further information, please refer to the relevant
WARNING
Inverter instruction manual.
Typical installation
L1 L2/N
PE
PE
Line
FILTER
Load
Cable length
as short as possible
Ground bonds
(remove any paint)
METAL PLATE
20096088
Installation
Ground bonds
(remove any paint)
INVERTER
PE L1 L2
U
VWPE
S8203
Motor cable
screened
M
3~
Fig. 31
28
Treatment of cables
Countermeasures against cable noise
The treatment of cables is the most important countermeasure.
The machinery manufacturers are requested
to examine the current structure of the cable lead - in.
 Use cables with woven screen
 The screen of the cable should be earthed with a large area.
 It is desirable to earth the screen of the cable by clamping the
cable to the earth plate.
 The screen must be earthed on both side of the cable (take
care for good earthing system).
S8201
Ground clamp
Example:
Number 1,2,3 show not proper ways to earth a cable screen.
S8202
GB
Ground bonds
(remove any paint)
Grounding plate
Fig. 32
Fig. 33