The Ground Fault Settings section is located in the upper right of the Protection screen. This section contains parameters for the
following values:
• Ground Fault Pickup (in Amps)
• Ground Fault Delay (in ms)
• I
t Curve for Ground Fault
2
• Ground Fault Alarm Pickup (in Amps)
• Ground Fault Alarm Delay (in ms)
The Breaker Controls section is located in the lower left of the Protection screen. This section contains "activate" buttons for Edit
Mode, Upload to Memory, Download from Memory, and Activate New Settings.
The Pickup Limits section is located in the lower right of the Protection screen. This section contains the min/max parameters for
Long Time Settings, Short Time Settings, Instantaneous Settings and Ground Fault/Alarm Settings. Min/max parameters are specific
to each breaker based on frame size, switching class, and rating plug. If an out of range value is entered, the input immediately
reverts back to the previous settings.

6.8 Active Alarms

The Alarm indication icon (upper right on all drilldown screens) appears only during an active alarm. If there is an active alarm, click-
ing on the Alarm Icon will open the WL Breaker Alarms screen. This screen displayed detailed information about the event, including
the Alarm Class, Current Alarm, Time Stamp, and Status. Every screen on the system has the Alarm Icon capability. The screens also
display clock, CPU status, CPU online status and System Modes settings.
6.8.1 Self-Reset Alarms
Alarms that automatically reset when condition is resolved.
• Withdrawn – disconnect
• Withdrawn – N/A
• Not Write Enabled
• Ready to close
• Door open
• Overload neutral
• Overload present
• Threshold exceeded
• Alarm present
• Load shedding alarm