The Trip Unit Alarms Currently Active section is located in the right of the Diagnostic screen. This section displays a green light to
indicate each of the following values:
• Overload Tripping Alarm
• Overload Neutral Alarm
• Load Shed Alarm
• Load Pick Up Alarm
• Phase Unbalance Current Alarm
• Microprocessor Fault
• Ground Fault Alarm
• Overtemperature Alarm
• Leading Overload Trip Alarm
• Short Time Pickup Alarm

6.7 Protection

All breaker protective parameters are viewed and set from the Protection screen. The VL Breaker has A parameters only.
The Long Time Settings section is located in the upper left of the Protection screen. This section contains parameters for the
following values:
• Long Time Pickup (in Amps)
• Long Time Delay (in Sec.)
• Thermal Memory
The Short Time Settings section is located in the mid left of the Protection screen. This section contains parameters for the
following values:
• Short Time Pickup (in Amps)
• Short Time Delay (in ms)
• I
t Curve for Short Time
2
The Instantaneous Settings section is located in the mid left of the Protection screen. This section contains parameters for
Instantaneous Pickup (in Amps). This parameter can be edited by clicking "Go To Breaker Instantaneous Settings" in the upper right
of the section.
Sm@rtGear™ IE User Manual
37