Active Alarms; Self-Reset Alarms; Latching Alarms - Siemens SmartGear IE User Manual

Table of Contents

Advertisement

On the Metering Settings screen, pickup limits are displayed to the right of individual parameters. Pickup limits are displayed for
Rated Primary Voltage in the Voltage section and Underflow Limit in the Long Time Mean section. If an out of range value is entered,
the input immediately reverts back to the previous settings.

5.10 Active Alarms

The Alarm indication icon (upper right of all drilldown screens) appears only during an active alarm. If there is an active alarm,
clicking on the Alarm Icon will open the WL Breaker Alarms screen. This screen displayed detailed information about the event,
including the Alarm Class, Current Alarm, Time Stamp, and Status. Every screen on the system has the Alarm Icon capability. The
screens also display clock, CPU status, CPU online status and System Modes settings.

5.10.1 Self-Reset Alarms

Alarms that automatically reset when condition is resolved.
• Withdrawn – disconnect
• Withdrawn – N/A
• Not Write Enabled
• Ready to close
• Door open
• Overload neutral
• Overload present
• Threshold exceeded
• Alarm present
• Load shedding alarm
• Trip coil monitor alarm
• Under voltage relay alarm

5.10.2 Latching Alarms

Alarms that stay active even if condition has been resolved until acknowledged/reset.
• External Trip
• Fail to Close
• Fail to Trip
• Withdrawn-Test
• Overcurrent Long Time
• Overcurrent Short Time
• Overcurrent Instantaneous
• Overcurrent Neutral
• Overcurrent Ground
• Extended Trip
• Fail to sync – if applicable
Sm@rtGear™ IE User Manual
33