FUNCTIONS

T muting (2 signals/4 sensors)

The activation of the Muting function occurs as a result of a rising edge on MUTING1
and MUTING2 inputs (the order depends on material direction). As reported in figure
below T
response time and less than 4s.
.
MUTING1
MUTING2
MUTING STATE
50
SH4 STANDARD MUTING
activation delay between MUTING1 and MUTING2 must be greater than
12
NOTE: See "Response Times" on page 78.
NOTE: Muting operations is ceased as soon as the signal on MUTING1 or
MUTING2 goes low.
T
min < T
12
ESPE
S4
S3
S2
S1
L
d1
D
Figure 40: Connection of sensors on MUTING1 and MUTING2 inputs in case of
bidirectional (T), four-sensors muting
t < muting timeout
t < muting timeout
< 4 s
T
min < T
12
12
12
Figure 39: T muting timings
24Vdc
V
S1
S3
24Vdc
S2
S4
24Vdc
0Vdc
24Vdc
0Vdc
ON
OFF
< 4 s
24Vdc
MUTING_1
24Vdc
MUTING_2
ESPE