L muting (2 signals/2 sensors)

The activation of the Muting function occurs as a result of a rising edge on MUTING1
and MUTING2 inputs. As reported in figure below T
ING1 and MUTING2 must be greater than response time and less than 4s.
NOTE: See "Response Times" on page 78.
T
is measured and then multiplied by 2 to calculate the muting timer. Muting opera-
12
tions is ceased when 2xT
If MUTING2 input goes low before MUTING1 muting is ceased immediately. Muting is
optionally ceased also when light curtain is free before the timer expires (Muting stop
condition parameter).
LIGHT CURTAIN
MUTING1
MUTING2
MUTING STATE
0s < T
< 4s
12
ESPE
S2
d1
D
Figure 38: Connection of sensors on MUTING1 and MUTING2 inputs in case of
monodirectional (L), two-sensors muting
timer expires, starting from falling edge on MUTING1 input.
12
2xT
12
Figure 37: L muting timings
S1
L
V
S1
S2
activation delay between MUT-
12
FREE
INTERCEPTED
24Vdc
0Vdc
24Vdc
0Vdc
ON
OFF
24Vdc
MUTING1
24Vdc
MUTING2
PRODUCT REFERENCE GUIDE
MUTING
ESPE
49