FUNCTIONS

EMISSION RANGE SELECTION (SH4-X-XXXX-X models only)

On Body models only (SH4-X-XXXX-X), TEST input (Pin 2 on transmitter unit) may be
used to set the Emission Range.
By default, SHORT Range is selected. To toggle between SHORT and LONG range, follow-
ing procedure must be followed: at runtime keep pin 2 input connected to 24V for more
than 2s and less than 5s to change range setting from Long to Short or viceversa. Emis-
sion Range setting is kept also after a power cycle.
TEST
EMISSION STATUS
0.5s after rising edge on TEST input emission is disabled, 2s after rising edge on TEST
input Range Change Request is activated and both S and L led are lit on user interface.
Range Change Request
If a falling edge is detected within 5s from rising edge, emitter unit reboots with the new
range.
If a falling edge is not detected within 5s from rising edge emitter unit locks into Range
setting failure Lockout without any change on range setting.
46
SH4 STANDARD MUTING
0.5s
2s
Figure 32: Emission Range Change Request timings
WARNING: When using SH4 Body models with operating distance lower
than 5m Short Range must be selected, otherwise safe operation is not
guaranteed.
RANGE
REBOOT
CHANGE
REQUEST
<5s
24Vdc
0V/FLOAT
ON
OFF